Plan Review Notes
Plan Review Notes For Permit 06090295
Permit Number 06090295
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-28 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 2} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS.
  
 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 4} INDICATE THE RATING OF THE EXISTING
 SERVICE.
  
 5} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(C), SEE REVIEWED
 PLAN, NORTH, EAST AND WEST COUNTER
 LOCATIONS.
  
 6} BATH CIRCUIT REQUIRED TO HAVE A 20
 AMP RECEPTACLE PER 210.11(C) (3),
 LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A)(1).
  
 7} SUNROOM REQUIRED TO HAVE RECEPTACLES
 PER 210.52(A)(1) AND (2). SEE REVIEWED
 SET FOR APPROXIMATE LOCATIONS.
  
 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]