| Notes |
| Date |
Text |
| 2006-09-28 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 2} PROVIDE A LOAD CALCULATION PER | | | 220.31, INCLUDE ADDED LOADS. | | | | | | 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC | | | AND 106.3.5.4(8) FBC. | | | | | | 4} INDICATE THE RATING OF THE EXISTING | | | SERVICE. | | | | | | 5} KITCHEN RECEPTACLE SPACING MUST | | | COMPLY WITH 210.52(C), SEE REVIEWED | | | PLAN, NORTH, EAST AND WEST COUNTER | | | LOCATIONS. | | | | | | 6} BATH CIRCUIT REQUIRED TO HAVE A 20 | | | AMP RECEPTACLE PER 210.11(C) (3), | | | LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A)(1). | | | | | | 7} SUNROOM REQUIRED TO HAVE RECEPTACLES | | | PER 210.52(A)(1) AND (2). SEE REVIEWED | | | SET FOR APPROXIMATE LOCATIONS. | | | | | | 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|