| Date |
Text |
| 2006-12-17 14:15:22 | *** UNSAT 2ND REVIEW *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW DONE |
| | BY BILL TROBAUGH AND MYSELF. PLEASE SUBMIT THE |
| | ELECTRICAL INFORMATION AS PREVIOUSLY REQUESTED. PLEASE |
| | KNOW THE INSTALLATION CAN NOT BE APPROVED UNTIL PROPER |
| | VERIFICATION OF ELECTRICAL CAN BE DONE TO SEE IF THERE |
| | IS ADEQUATE SPACE AND ELECTRICAL FOR EQUIPMENT BEING |
| | PROPOSED. |
| | THIS MUST BE VERIFIED AT THIS TIME. |
| | PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR |
| | EQUIPMENT BEING INSTALLED. 90.7, 110.3 |
| | PLEASE INDICATE CIRCUITING WHERE EQUIPMENT IS BEING FED |
| | FROM, PLEASE INDICATE EXISTING LOAD AND NEW LOAD BEING |
| | ADDED. |
| | PLEASE INDICATECONDUCTORS, SIZES ETC. |
| | 240.4, 310.16, 408.4,220, |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |