| Plan Review Notes For Permit 06090287 |
| Permit Number |
06090287 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-18 15:53:26 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) PROJECT IS LOCATED IN AN 'A8' FLOOD | | | ZONE AN ELEVATION CERTIFICATE WILL BE | | | REQUIRED. EQUIPMENT IS REQUIRED TO BE | | | LOCATED 6" ABOVE BASE FLOOD ELEVATION. | | | | | | 3)AN INTERNAL PRESSURE COEFFICENT OF + / - 0.18 IS | | | SPECIFIED ON THE PLANS. THIS INDICATES THAT THIS IS AN | | | ENCLOSED STRUCTURE, WHICH IT IS NOT. PLEASE CORRECT. | | | SEE FBC 1603.1.4 AND ASCE 7-02. | | | | | | 4) SUBMIT THE MANUFACTURES SPECIFICATIONS INDICATING | | | THE ATTACHMENTS OF THE EQUIPMENT TO THE CONCRETE PAD. | | | FBC 1609.1.3. | | | | | | 5) SEE COMMENTS OF OTHER TRADES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|