| Plan Review Notes For Permit 06090287 |
| Permit Number |
06090287 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-13 17:45:41 | DENIED | | | REFERENCES: FBC-2004 CHAPTER 1 | | | FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. PLEASE INDICATE WHAT TYPE OF EQUIPMENT WILL BE | | | WASHED AT THE WASH PIT. SECTION106.1.1. | | | | | | 2. MORE INFORMATION IS REQUIRED. WILL THE SYSTEM BE | | | CONNECTED TO A POTABLE WATER SOURCE OR A SANITARY | | | DRAINAGE SYSTEM? SECTION 106.1.1. IF THE SYSTEM IS | | | CONNECTED TO THE POTABLE WATER, AN RPZV BACKFLOW WILL | | | BE REQUIRED. SECTION 608.13.2. | | | | | | 3. PLANS INDICATE AN OIL TRAP. PLEASE CONTACT LYNN | | | MASSON, ENVIRONMENTAL COMPLIANCE TO SEE IF AN OIL | | | INTERCEPTOR WILL BE REQUIRED IF THE SYSTEM WILL BE | | | CONNECTED TO THE SANITARY SEWER SYSTEM. (561) 822-2271, | | | OR FAX (561) 822-2279, OR E-MAIL [email protected]. WASTE | | | ORD. #3434. IF THE SYSTEM IS NOT CONNECTED TO THE SANT. | | | SEWER, PLEASE INDICATE HOW THE OIL WILL BE DISPOSED. | | | SECTION 106.1.1. | | | | | | 4. INDICATE HOW THE SLUDGE WILL BE DISPOSED. SECTION | | | 106.1.1. | | | | | | 5. PLEASE SEE COMMENTS BY DEWEY PALMER CONCERNING THE | | | FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUTES | | | PERTAINING TO THE DESIGNER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] | | | |
|