Plan Review Notes
Plan Review Notes For Permit 06090272
Permit Number 06090272
Review Stop P
Sequence Number 3
Notes
Date Text
2008-02-21 14:56:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 DETAIL SUBMITTED.
  
 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT
 THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT
 OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO
 RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE DRINKING FOUNTAIN IS NOT
 VENTED AS SHOWN. SEE RED LINE CORRECTION INDICATED ON
 ONE SHEET FOR AN EXAMPLE OF A RISER DIAGRAM THAT MEETS
 CODE AT THE DRINKING FOUNTAIN. SECTION 901.2.1.
  
 3. OK
  
 REVIEW BY KEN STEVENS