| Plan Review Notes For Permit 06090272 |
| Permit Number |
06090272 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-27 16:53:52 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT | | | THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT | | | OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO | | | RESPONSE, NOT ADDRESSED. | | | | | | 3. SUBMIT A WATER RISER DIAGRAM ISOMETRIC SHOWING PIPE | | | SIZE, VALVES, WATER HAMMER IF REQUIRED BY SECTION | | | 604.9, AND POINT OF CONNCECTION. SECTION | | | 106.3.4.1.3(3)(13). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|