2006-10-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)DOCUMENTS PREPARED BY AN ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS.
 SHEETS A4 THROUGH A9 PREPARED BY REG
 ARCHITECTS APPEAR TO BE EXISTING
 BUILDING DRAWINGS, SUBMITTED FOR
 REFERENCE.EITHER HAVE THEM SIGNED AND
 SEALED, OR INCORPORATE THE INFORMATION
 REQUIRED TO SHOW SCOPE OF WORK AND CODE
 COMPLIANCE INTO MR. YECKES? DRAWINGS.
  
 2.)WHAT WILL BE STORED IN THE NEW
 STORAGE ROOM?INDICATE NON HAZARDOUS
 STORAGE ON THE PLAN OR DECLARE A STORAGE
 OCCUPANCY AND SHOW SEPARATION FBC TABLE
 302.3.2.
  
 3.)IS THE STORAGE AREA ACCESSORY?SEE
 FBC 302.2; IF THIS AREA IS ACCESSORY,
 SHOW COMPLIANCE.OTHERWISE SHOW
 REQUIRED OCCUPANCY SEPARATION FBC TABLE
 302.3.2.
  
 4.)PROVIDE A CODE SUMMARY; BUILDING
 HEIGHT, AREA, OCCUPANCY, BUILDING TYPE,
 FIRE SPRINKLER INFORMATION.DECLARE A
 SQUARE FOOT AREA FOR THE NEW STORAGE.
  
 5.)PROVIDE A DETAIL FOR THE NEW 4IN
 WALL AND THE NEW 8IN WALL.
  
 6.)DECLARE WIND DESIGN CRITERIA,
 FBC1603.1.4.
  
 7.)THE PLANS STATE THAT THE EXISTING
 WATER FOUNTAIN WILL BE RELOCATED.
 PROVIDE A DETAIL FOR THE WATER FOUNTAIN
 SHOWING COMPLIANCE WITH ALL REQUIREMENTS
 OF FBC11-4.15.
  
 8.)THIS IS A MAJOR WORKING DRAWING
 REVIEW.APPLICATION BY A CONTRACTOR
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 9.)DECLARE GOVERNING CODE, INCLUDING
 FBC EB, AND DECLARE LEVEL OF ALTERATION
 FBC EB 3.
  
 10.)PROVIDE A DETAIL FOR THE WOOD
 LOUVERS.
  
  