| Plan Review Notes For Permit 06090267 |
| Permit Number |
06090267 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-15 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PLAN REVIEW: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | NOTE: THIS INCLUDES THE EXISTING SYSTEM | | | AS WELL AS THE PROPOSED SYSTEM IN ORDER | | | TO VERIFY THE LONGEST LENGTH. | | | | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | NOTE: NEED BTU LOAD OF EXISTING SYSTEM | | | AS WELL AS THE PROPOSED. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | NOTE: THIS INCLUDES THE EXISTING SYSTEM | | | AS WELL AS THE PROPOSED. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | |
|