| 2006-10-12 18:10:23 | BUILDING REVIEW CHECKLIST: |
| | 1- SPECIFY SAFETY GLASS BY MASTER BATH BATHTUB. SEC. |
| | R308.4 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 2- UPDATE STRUCTURAL NOTE #2(C). NEED TO REFERENCE ASCE |
| | 7-02 NOT ASCE 7-98. |
| | |
| | 3- REVISE STRUCTURAL NOTE #14. NAIL SIZE IS NOT LONG |
| | ENOUGH ACCORDING TO ASTM C-926 AND ASTM C-1063. NEED |
| | FASTENER THAT IS LONG ENOUGH TO PROVIDE MIN. EMBEDMENT |
| | OF 1 3/4" INTO TRUSS. REVISE AS REQUIRED. ALSO, CLARIFY |
| | NOTE REGARDING VENTING. STUCCO SOFFIT HAS NOTHING TO DO |
| | WITH PLYWOOD VENTING? |
| | |
| | 4- OWES $4.46 FOR RADON FEES. |
| | |
| | 5- SOIL TEST REPORT SUBMITTED: |
| | A) NEED 2 COPIES WITH ORIGINAL SEAL, SIGNATURE AND |
| | DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.B) |
| | NEED ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION IN |
| | THE REPORT LETTERHEAD AS REQUIRED BY FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED |
| | COPY. |
| | C) REPORT SAYS THAT PROPOSED CONSTRUCTION IS MASONRY. |
| | PLANS SHOW WOOD FRAME CONSTRUCTION. CLARIFY AND REVISE |
| | AS REQUIRED. |
| | |
| | 6- TRUSS DRAWINGSWILL NEED TO BE SUBMITTED PRIOR TO |
| | INSTALLATION AS REQUIRED BY SEC. R802.10 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- SURVEY WITH PROPOSED ADDITION DON'T MATCH PLANS. |
| | REVISE AS REQUIRED. ONLY 2 COPIES REQUIRED. SEE |
| | COMMENTS FROM ZONING REVIEW. |
| | |
| | 8- ENERGY CALCULATIONS PAGE 2.MINIMUM INSULATION |
| | REQUIRED FOR 2"X6" WALL IS R-19, NOT R-11. REVISE AS |
| | REQUIRED. |
| | |
| | 9- REVISE TYPICAL WALL SECTION ON DRAWING 2/3 TO |
| | REFLECT THE R-19 INSULATION AS REQUIRED BY ENERGY |
| | CALCULATIONS. |
| | |
| | 10- SHOW IN PLANS SPECIFIC LOCATION AND SIZE OF |
| | VENTILATION OPENINGS THAT COMPLY WITH SEC. R806.2. |
| | SPECIFICATIONS SHOWN ON PLAN "VENTILATIONTO MATCH |
| | EXISTING" IS NOT ENOUGH INFORMATION TO VERIFY |
| | COMPLIANCE. PROVIDE VENTILATION CALCULATIONS. |
| | |
| | 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | NOAS 03-0514.01 AND 02-0701.12 WERE SIGNED AND SEALED |
| | BY AN ARCHITECT WHO HAS NOTHING TO DO WITH THIS JOB. ON |
| | THE OTHER HAND,NOA'S NO NEED TO BE SIGNED AND SEALED |
| | AND ONLY THE PROFESSIONAL RESPONSIBLE OF THE DESIGN OF |
| | THE PRODUCT IS ALLOWED TO SIGN AND SEAL IT. |
| | |
| | 12- ALL PRODUCT APPROVALS NEED TO BE APPROVED IN |
| | WRITTING BY DESIGNER OF RECORD FOR THIS PROJECT. BUCK |
| | ENGINEERING STAMP ALONE IS NOT ENOUGH INFORMATION TO |
| | SHOW ENGINEER'S APPROVAL.STAMP DOESN'T IDENTIFY WHAT |
| | IS THE STAMP FOR AND IS NOT SIGNED/INITIALIZED BY THE |
| | ENGINEER.CLEARLY SPECIFY THAT PRODUCT WAS REVIEWED |
| | AND APPROVEDAS REQUIRED BY SEC. 106.3.3 OF CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 13- BUCK ENGINEERING INC NEED TO PROVIDE THE FIRM |
| | CERTIFICATE OF AUTHORIZATION AS REQUIRED BY FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED |
| | COPY. |
| | |
| | 14- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR:A) |
| | SINGLE HUNG WINDOWS. NEED TO PROVIDE NOA THAT MATCHES |
| | ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 239. |
| | |
| | B) WINDOW MULLIONS. NEED TO PROVIDE NOA THAT MATCHES |
| | ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 261. |
| | ALSO, NOA 02-0701.05 SUBMITTED EXPIRED ON 06/28/06. |
| | |
| | C) FLAT ROOF SYSTEM. |
| | * NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLY FROM THE |
| | NOA TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. *** |
| | NOTE: KEEP IN MIND THAT PLANS CALL FOR INSULATED |
| | ASSEMBLY. SEE TYPICAL WALL SECTION IN PLANS. **NEED TO |
| | PROVIDE RAS 117 CALCULATIONS DONE ONLY BY ANY OF THE |
| | PROFESSIONALS LISTED ON GENERAL LIMITATION #7 OF |
| | PRODUCT APPROVAL. SEE LAST PAGE OF THE NOA. |
| | |
| | D) FIXED WINDOWS. NEED TO PROVIDE NOA THAT MATCHES |
| | ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 243.NOA |
| | 01-0102.01 EXPIRED ON 09/13/06. |
| | |
| | E) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS AND |
| | DETAILS. SEE PLANS. PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND DRAWING SHOWING SPECIFIC |
| | CONNECTORS. NO NEED TO INCLUDE COMPLETEREPORT. |
| | |
| | 15- WEST ELEVATION ON SHEET 1/3 SHOWS MASTER BEDROOM |
| | DOOR AS 8'-0" HIGH DOOR. FLOOR PLAN CALLS FOR 6'-8" |
| | HIGH DOOR. REVISE AS REQUIRED TO MATCH. |
| | |
| | 16- SHEET 2/3: |
| | A) TYPICAL WALL SECTION : REVISE FASTENER FOR MTS20 |
| | CONNECTOR SPECIFIED. THIS IS WOOD FRAME CONSTRUCTION, |
| | NOT MASONRY. THEREFORE TITEN FASTENERS ARE NOT USED. |
| | SEE CATALOGUE FOR PROPER NUMBER AND TYPE OF FATENERS. |
| | |
| | B) TRUSS TIE DOWN SCHEDULE: SEE CURRENT CATALOGUE AND |
| | REVISE NUMBER,TYPEAND DESIGN PRESSURESFOR ALL |
| | CONNECTORS. OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS FOR NUMBERS THAT DIFFER FROM THOSE TESTED AND |
| | PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |