Plan Review Notes
Plan Review Notes For Permit 06090266
Permit Number 06090266
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-12 18:10:23BUILDING REVIEW CHECKLIST:
 1- SPECIFY SAFETY GLASS BY MASTER BATH BATHTUB. SEC.
 R308.4 2004 FLORIDA RESIDENTIAL CODE.
  
 2- UPDATE STRUCTURAL NOTE #2(C). NEED TO REFERENCE ASCE
 7-02 NOT ASCE 7-98.
  
 3- REVISE STRUCTURAL NOTE #14. NAIL SIZE IS NOT LONG
 ENOUGH ACCORDING TO ASTM C-926 AND ASTM C-1063. NEED
 FASTENER THAT IS LONG ENOUGH TO PROVIDE MIN. EMBEDMENT
 OF 1 3/4" INTO TRUSS. REVISE AS REQUIRED. ALSO, CLARIFY
 NOTE REGARDING VENTING. STUCCO SOFFIT HAS NOTHING TO DO
 WITH PLYWOOD VENTING?
  
 4- OWES $4.46 FOR RADON FEES.
  
 5- SOIL TEST REPORT SUBMITTED:
 A) NEED 2 COPIES WITH ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.B)
 NEED ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION IN
 THE REPORT LETTERHEAD AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED
 COPY.
 C) REPORT SAYS THAT PROPOSED CONSTRUCTION IS MASONRY.
 PLANS SHOW WOOD FRAME CONSTRUCTION. CLARIFY AND REVISE
 AS REQUIRED.
  
 6- TRUSS DRAWINGSWILL NEED TO BE SUBMITTED PRIOR TO
 INSTALLATION AS REQUIRED BY SEC. R802.10 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- SURVEY WITH PROPOSED ADDITION DON'T MATCH PLANS.
 REVISE AS REQUIRED. ONLY 2 COPIES REQUIRED. SEE
 COMMENTS FROM ZONING REVIEW.
  
 8- ENERGY CALCULATIONS PAGE 2.MINIMUM INSULATION
 REQUIRED FOR 2"X6" WALL IS R-19, NOT R-11. REVISE AS
 REQUIRED.
  
 9- REVISE TYPICAL WALL SECTION ON DRAWING 2/3 TO
 REFLECT THE R-19 INSULATION AS REQUIRED BY ENERGY
 CALCULATIONS.
  
 10- SHOW IN PLANS SPECIFIC LOCATION AND SIZE OF
 VENTILATION OPENINGS THAT COMPLY WITH SEC. R806.2.
 SPECIFICATIONS SHOWN ON PLAN "VENTILATIONTO MATCH
 EXISTING" IS NOT ENOUGH INFORMATION TO VERIFY
 COMPLIANCE. PROVIDE VENTILATION CALCULATIONS.
  
 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 NOAS 03-0514.01 AND 02-0701.12 WERE SIGNED AND SEALED
 BY AN ARCHITECT WHO HAS NOTHING TO DO WITH THIS JOB. ON
 THE OTHER HAND,NOA'S NO NEED TO BE SIGNED AND SEALED
 AND ONLY THE PROFESSIONAL RESPONSIBLE OF THE DESIGN OF
 THE PRODUCT IS ALLOWED TO SIGN AND SEAL IT.
  
 12- ALL PRODUCT APPROVALS NEED TO BE APPROVED IN
 WRITTING BY DESIGNER OF RECORD FOR THIS PROJECT. BUCK
 ENGINEERING STAMP ALONE IS NOT ENOUGH INFORMATION TO
 SHOW ENGINEER'S APPROVAL.STAMP DOESN'T IDENTIFY WHAT
 IS THE STAMP FOR AND IS NOT SIGNED/INITIALIZED BY THE
 ENGINEER.CLEARLY SPECIFY THAT PRODUCT WAS REVIEWED
 AND APPROVEDAS REQUIRED BY SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 13- BUCK ENGINEERING INC NEED TO PROVIDE THE FIRM
 CERTIFICATE OF AUTHORIZATION AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED
 COPY.
  
 14- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR:A)
 SINGLE HUNG WINDOWS. NEED TO PROVIDE NOA THAT MATCHES
 ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 239.
  
 B) WINDOW MULLIONS. NEED TO PROVIDE NOA THAT MATCHES
 ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 261.
 ALSO, NOA 02-0701.05 SUBMITTED EXPIRED ON 06/28/06.
  
 C) FLAT ROOF SYSTEM.
 * NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLY FROM THE
 NOA TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. ***
 NOTE: KEEP IN MIND THAT PLANS CALL FOR INSULATED
 ASSEMBLY. SEE TYPICAL WALL SECTION IN PLANS. **NEED TO
 PROVIDE RAS 117 CALCULATIONS DONE ONLY BY ANY OF THE
 PROFESSIONALS LISTED ON GENERAL LIMITATION #7 OF
 PRODUCT APPROVAL. SEE LAST PAGE OF THE NOA.
  
 D) FIXED WINDOWS. NEED TO PROVIDE NOA THAT MATCHES
 ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 243.NOA
 01-0102.01 EXPIRED ON 09/13/06.
  
 E) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS AND
 DETAILS. SEE PLANS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND DRAWING SHOWING SPECIFIC
 CONNECTORS. NO NEED TO INCLUDE COMPLETEREPORT.
  
 15- WEST ELEVATION ON SHEET 1/3 SHOWS MASTER BEDROOM
 DOOR AS 8'-0" HIGH DOOR. FLOOR PLAN CALLS FOR 6'-8"
 HIGH DOOR. REVISE AS REQUIRED TO MATCH.
  
 16- SHEET 2/3:
 A) TYPICAL WALL SECTION : REVISE FASTENER FOR MTS20
 CONNECTOR SPECIFIED. THIS IS WOOD FRAME CONSTRUCTION,
 NOT MASONRY. THEREFORE TITEN FASTENERS ARE NOT USED.
 SEE CATALOGUE FOR PROPER NUMBER AND TYPE OF FATENERS.
  
 B) TRUSS TIE DOWN SCHEDULE: SEE CURRENT CATALOGUE AND
 REVISE NUMBER,TYPEAND DESIGN PRESSURESFOR ALL
 CONNECTORS. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR NUMBERS THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712