| Date |
Text |
| 2008-02-05 15:35:06 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FBC-2004 EXISTING BLDG CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | COMMENT NUMBERS TO STAY THE SAME. |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW*** |
| | |
| | ********FROM PREVIOUS REVIEWS: 4TH REVIEW*** |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| | PER TABLES 1004.2 AND 403.1. |
| | ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3 |
| | OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR |
| | THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE |
| | THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE |
| | TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE |
| | NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE |
| | TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY |
| | INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE |
| | TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL |
| | OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN & |
| | WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5 |
| | WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10 |
| | WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY |
| | REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS |
| | OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY |
| | SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING |
| | FACILITIES. |
| | ********RESPONSE NOTED, BUT THE CALCULATIONS ONLY |
| | ACCOUNT FOR 3233SF, BUT THE TOTAL AREA IS INDICATED AS |
| | 10,411SF. INDICATE WHERE THE OTHER 7178SF REQUIRED IN |
| | THE CALCULATION IS INDICATED. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. OK |
| | 2B. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION |
| | 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING |
| | INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| | BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY |
| | OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY. |
| | PLEASE CLARIFY. |
| | ********RESPONSE NOTED, BUT THE TOILET ROOMS ON THE |
| | SECOND FLOOR SHALL BE ACCESSIBLE PER SECTION 806.1 OF |
| | THE EXISTING BUILDING CODE |
| | |
| | REVIEW BY KEN STEVENS |