| 2007-11-24 17:23:29 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | COMMENT NUMBERS TO STAY THE SAME. |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW*** |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| | PER TABLES 1004.2 AND 403.1. |
| | ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3 |
| | OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR |
| | THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE |
| | THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE |
| | TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. ******RESPONSE |
| | NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. IS THE |
| | TOTAL AREA OF THE BUILDING TO BE A-3 OCCUPANCY |
| | INCLUDING ALL THE OFFICES ON THE SECOND FLOOR? THE |
| | TOTAL SQUARE FOOTAGE IS 10411SF @ 7NET THE TOTAL |
| | OCCUPANCY IS 1488. THIS NUMBER DIVIDED BY 2, (MEN & |
| | WOMEN), COMES TO 744 EACH. 744 DIVIDED BY 150 EQUALS 5 |
| | WATER CLOSETS FOR MEN AND 744 DIVIDED BY 75 EQUALS 10 |
| | WATER CLOSETS FOR WOMEN TO ACHIEVE POTTY PARITY |
| | REQUIRED BY SECTION 403.1.1. THAT SAID, IF THERE IS |
| | OTHER OCCUPANCIES BESIDES ASSEMBLY PLEASE INDICATE BY |
| | SUBMITTING CALCULATIONS FOR MINIMUM PLUMBING |
| | FACILITIES. |
| | |
| | 5. OK |
| | |
| | 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS |
| | IS NOT INDICATED ON PLANS. |
| | ****NOT ADDRESSED |
| | ******RESPONSE NOTED, BUT SECTION 403.1.1 IS NOT |
| | COMPLIED WITH. THE CODE SECTION STATES "IN ASSEMBLY |
| | OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO THE PUBLIC |
| | MUST HAVE A RATIO OF 3:2 WATER CLOSETS PROVIDED FOR |
| | WOMEN AS THE TOTAL OF WATER CLOSETS AND URINALS |
| | PROVIDED FOR MEN". POTTY PARITY CALCULATIONS SUBMITTED |
| | HAVE 4 WATER CLOSETS FOR MEN TO 3 WATER CLOSETS FOR |
| | WOMEN. |
| | |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHT 3/5 NEW MEN'S TOILET ROOM STALL DOES NOT COMPLY |
| | WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3 |
| | EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE |
| | TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION |
| | 11-4.22.3. |
| | ****RESPONSE NOTED, BUT THE TURNING AREA IS NOT SHOWN |
| | IN THE TOILET ROOMS AS REQUIRED. (NOT REQUIRED IN THE |
| | ACCESSIBLE STALL). |
| | ******RESPONSE NOTED, BUT THE STALL STILL DOES NOT |
| | COMPLY WITH FIGURE 30E. THE LAV IS NOT ALLOWED IN THE |
| | CLEAR FLOOR SPACE OF THE WATER CLOSET. FIVE FEET OF |
| | CLEAR FLOOR SPACE FROM THE WALL ADJACENT TO THE WATER |
| | CLOSET TO THE SIDE OF THE LAV. THE LAV CAN NOT BE IN |
| | THE CLEAR FLOOR SPACE OF THE WATER CLOSET. |
| | |
| | 10. OK |
| | |
| | 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE |
| | WITH 11-4.18 AND ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING SECTIONS WERE NOT |
| | ADDRESSED: |
| | A. OK |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ******RESPONSE NOTED, BUT THE CONTROL HEIGHT IS |
| | REQUIRED. |
| | |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. OK |
| | |
| | 2B. SHT 3/5 MEN'S TOILET ROOM ACCESSIBLE STALL. THE |
| | ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER, DIAGONAL |
| | TO THE DOOR. SECTION 11-4.17.3 EXCEPTION (2). |
| | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1C. IN RELATIONSHIP TO THE CHANGE OF OCCUPANCY, SECTION |
| | 806.1 OF THE FLORIDA BUILDING CODE EXISTING BUILDING |
| | INDICATES "ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| | BUILDING. IS THE SECOND FLOOR CONSIDERED ASSEMBLY |
| | OCCUPANCY, AND WHAT WAS THE OCCUPANCY PREVIOUSLY. |
| | PLEASE CLARIFY. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |