| 2007-03-19 17:42:32 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | COMMENT NUMBERS TO STAY THE SAME. |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| | PER TABLES 1004.2 AND 403.1. |
| | ****NOT ADDRESSED. IT SEEMS THAT THERE IS MORE THAN A-3 |
| | OCCUPANCY. PLEASE SEE SECTION 403.1.1 POTTY PARITY FOR |
| | THE A-3 OCCUPANCY. INDICATE ALL OCUPANCIES AND INDICATE |
| | THE SQUARE FOOTAGE OF ALL OCCUPANCIES AS WELL AS THE |
| | TOTAL OCCUPANCY LOAD OF EACH OCCUPANCY. |
| | |
| | 5. OK |
| | |
| | 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS |
| | IS NOT INDICATED ON PLANS. |
| | ****NOT ADDRESSED |
| | |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHT 3/5 NEW MEN'S TOILET ROOM STALL DOES NOT COMPLY |
| | WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3 |
| | EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE |
| | TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION |
| | 11-4.22.3. |
| | ****RESPONSE NOTED, BUT THE TURNING AREA IS NOT SHOWN |
| | IN THE TOILET ROOMS AS REQUIRED. (NOT REQUIRED IN THE |
| | ACCESSIBLE STALL). |
| | |
| | 10. SHT 3/5 ELEVATIONS FOR WATER CLOSETS AND LAVS. SHOW |
| | THE FOLLOWING INFORMATION: |
| | FOR W/C'S |
| | A. OK |
| | B. 11-4.16.3 HEIGHT (SHOWN AS 20") (NOT ADDRESSED) |
| | (17" TO 19") |
| | C. OK |
| | D. 11-4.16.5 FLUSH CONTROLS (NOT ADDRESSED) |
| | FOR LAV'S |
| | A. 11-4.19.3 CLEAR FLOOR SPACE (NOT ADDRESSED)B. |
| | 11-4.19.5 FAUCETS (NOT ADDRESSED) |
| | |
| | 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE |
| | WITH 11-4.18 AND ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING SECTIONS WERE NOT |
| | ADDRESSED: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | |
| | 12. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS, AS WELL AS |
| | 11-4.1.3(10)(B) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING IF THE DRINKING FOUNTAIN |
| | IS NOT A HIGH/LOW UNIT. |
| | ****RESPONSE NOTED, BUT A DETAIL FOR THE ACCESSIBLE |
| | DRINKING FOUNTAIN HAS NOT BEEN SUBMITTED. |
| | |
| | 13. SHT 3/5 PLUMBING SANITARY RISER DIAGRAM. URINALS |
| | ARE NOT VENTED. SECTION 901.2.1. |
| | ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS.--THE FLOOR PLAN SHOWS TWO URINALS, |
| | BUT THE RISER DIAGRAM SHOW THREE URINALS.--THE |
| | DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM. -- |
| | THE LAV IN THEACCESSIBLE STALL IS NOT VENTED.-- THE |
| | URINALS STILL ARE NOT VENTED.SECTION 106.1.1. (SEE |
| | RED LINE MARKINGS ON THE COPY OF THE RISER DIAGRAM. |
| | |
| | 14. SUBMIT A WATER RISER DIAGRAM ISOMETRIC. SHOW ALL |
| | PIPE SIZES, VALVES, AND WATER HAMMER ARRESTORS AS |
| | REQUIRED BY SECTION 604.9. IF WATER HAMMER ARRESTORS |
| | ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE FIXTURE |
| | IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | ****NO RESPONSE. NOT ADDRESSED. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. ALL SHEETS. THE ADDRESS FOR THE ENGINEER DOES NOT |
| | REFLECT THE ADDRESS ON THE FLORIDA DBPR WEBSITE. PLEASE |
| | UPDATE THE WEBSITE OR CHANGE THE TITLE BLOCK. FAC |
| | 61G15-23.002(2)&FS 471.025. (SEE ATTACHED DBPR |
| | WEBSITE SHEET). |
| | |
| | 2B. SHT 3/5 MEN'S TOILET ROOM ACCESSIBLE STALL. THE |
| | ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER, DIAGONAL |
| | TO THE DOOR. SECTION 11-4.17.3 EXCEPTION (2). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |