| 2007-03-18 14:09:15 | ** UNSAT ** |
| | |
| | ** PLEASE KNOW THAT THIS IS A CHANGE IN OCCUPANCY AND |
| | ALL ELECTRICAL WILL BE REQUIRED TO MEET THE CURRENT |
| | CODES ADOPTED WHEN PERMIT WAS APPLIED. |
| | THE PERMIT DESCRIPTION ON COMPUTER NOW INDICATES BUILD |
| | OUT FOR NEW CHURCH. |
| | |
| | *********************************** |
| | ** PLEASE SEE PLANS ARE STAMPED FROM PALM BEACH COUNTY |
| | FOR IMPACT FEES WHICH INDICATE *EXISTING* USEAND |
| | PLANS SUBMITTED TO PALM BEACH COUNTY ALSO INDICATE |
| | EXISTING USE AS A CHURCH. PLEASE KNOW THIS WILL BE |
| | FORWARD TO PALM BEACH COUNTY FOR THIS USE AS NEW AS IT |
| | IS NOT EXISTING. |
| | *************************************** |
| | |
| | 1) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS |
| | ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS |
| | FOLLOWS. |
| | 2004 FBC |
| | 2002 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND |
| | OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON TITLE BLOCKS FOR THE COMPANY |
| | LISTED AS MCR PROFESSIONAL ENGINEERING INC. PLEASE SEE |
| | SHEET IS ATTACHED FROM THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION WITH THE LICENSE INFORMATION AS |
| | NEED. PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE |
| | SOME AREAS WHICH DO NOT INDICATE ANY LIGHTING CONTROLS. |
| | PLEASE SEE AREAS OF STAIRS WHICH WILL ALSO BE NOTED IN |
| | ANOTHER NOTE FOR LIFE SAFETY AND EGRESS WHICH WILL BE |
| | REQUIRED TO CONTAIN A AUTOMATED DEVICE FOR OCCUPANTS |
| | WHERE SWITCHED. |
| | PLEASE VERIFY THE COVERAGE ON THE DEVICES AS NOTED AS |
| | THE COVERAGE IN LARGER BATHROOMS WHICH CONTAIN MULTIPLE |
| | STALLS AND ALSO HALLWAY AREAS WHICH INDICATE WALL |
| | MOUNTED DEVICES. PLEASE VERIFY IF THESE DEVICES AS |
| | SHOWN WILL PROVIDE THE COVERAGE AS NEEDED. |
| | PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. |
| | PLEASE SEE 13-415.1.AB.1, PLEASE SEE MISSING ENERGY |
| | CALCULATIONS FOR BUILD OUT OF NEW CHURCH. |
| | PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT |
| | INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE |
| | THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE |
| | SUBMITTED. |
| | * PLEASE SEE ALL OF CHAPTER 13. |
| | 13-103.1.1.1 |
| | |
| | 4) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK NEEDS TO BE DECLARED. UNABLE TO VERIFY AT THIS |
| | TIME. BASED ON THE SCOPE OF ELECTRICAL WORK AND OTHER |
| | TRADES THE APPLIED VALUE IS LOW. PLEASE SEE FBC 108.3 |
| | ADMIN SECTION. |
| | |
| | 5) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND RISER |
| | FOR THE ELECTRICAL SERVICE AS SHOWN AND NOTED. PLEASE |
| | KNOW THERE ARE MANY NOTES ON PLANS TO VERIFY SERVICE, |
| | CONDUCTORS, AND FEEDERS ETC. PLEASE KNOW THAT ALL THE |
| | VERIFICATION IS REQUIRED BEFORE PERMIT ISSUANCE AND |
| | SHALL BE STATED ON PLANS AS REQUIRED FOR NEW BUILD |
| | OUT. |
| | PLEASE SEE RISER MENTIONS NEW PANELS, YET MDP MENTIONS |
| | PANELS AS EXISTING? |
| | THESE ARE PANELS WHICH WERE INSTALLED WITHOUT PERMITS, |
| | THEY SHALL BE INCLUDED AS *NEW* ON THESE RECORD SETS OF |
| | PLANS. |
| | PLEASE SEE MDP AND PLANS DO NOT MATCH AND PROVIDE |
| | ENOUGH INFORMATION FOR THE PANELS SHOWN FOR AIR |
| | HANDLING UNITS 1,2 AND 3. |
| | (PLEASE ALSO SEE THE NEXT COMMENT #6.) |
| | PLEASE CLARIFY SEVERAL PANELS ON PLANS WHICH MENTIONS |
| | *EXIST PANEL, NOT USED*? PLEASE SEE NO INFORMATION IS |
| | PROVIDED FOR THESE AND WHETHER OR NOT THESE PANELS ARE |
| | BEING REMOVED? PLEASE INDICATE IF THEY. PLEASE INDICATE |
| | IF THEY ARE BEING REMOVED, IF NOT THEN PLEASE INCLUDE |
| | ON PANEL SCHEDULES, PLANS, RISER ETC. |
| | |
| | 6) NOTE: PLEASE CORRELATE ALL LOADS FOR AIR |
| | CONDITIONING EQUIPMENT. PLEASE SEE THE LOAD |
| | CALCULATIONS INDICATE A TOTAL OF 27KVA, YET THE PANEL |
| | SCHEDULE FOR PANEL *B* ALONE SHOWS 30KVA FOR A/C |
| | EQUIPMENT. PLEASE SEE THE LOAD ON CIRCUIT 1 ON THE MDP |
| | INDICATES 18KVA WHICH EXCEEDS THE RATING OF THE OVER |
| | CURRENT PROTECTION DEVICE AS SHOWN FEEDING AHU 1, 2 AND |
| | 3? |
| | PLEASE SEE NOTE ABOVE AS INFORMATION FOR THE FEEDERS |
| | ETC TO THE AHU PANELS NEEDS TO BE SUBMITTED FOR REVIEW. |
| | NOT ENOUGH INFORMATION IS SUBMITTED FOR FULL REVIEW OF |
| | CODE COMPLIANCE. |
| | NEC 220, 424.3, 215.5, ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | ** PLEASE ALSO VERIFY THE CONDENSING UNITS WHICH ARE |
| | SHOWN AS 3-PHASE AND AIR HANDLING UNITS AS SINGLE PHASE |
| | AND CONDENSING UNITS BEING SHOWN AS 3-PHASE WITH AIR |
| | HANDLING UNITS TO A SINGLE PHASE PANEL?? |
| | |
| | 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL |
| | SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT |
| | FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN |
| | FROM THE CODE. |
| | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 8) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS MEETING NFPA-101 7.8 AND 7.9. |
| | PLEASE SEE 7.8.1.3 AND 7.9.2.2 FOR STAIR AREAS. |
| | PLEASE SHOW LIGHTING LEVELS UNDER NORMAL AND EMERGENCY |
| | CONDITIONS. |
| | PLEASE ALSO SEE NOTE ABOVE WITH RESPECT TO CONTROLS FOR |
| | LIGHTING WHICH SHALL NOT LEAVE ANY ONE AREA IN TOTAL |
| | DARKNESS BASED ON THE SWITCHING OF A DEVICE, TRIPPING |
| | OF A BREAKER ETC. |
| | PLEASE SEE BUILDING COMMENTS FOR POSSIBLE 2ND MEANS OF |
| | EGRESS WHICH MAY BE REQUIRED. PLEASE KNOW ANY OTHER |
| | EGRESS PATH FROM SECOND FLOOR WHICH MAY APPEARS TO |
| | PLACE OCCUPANTS OVER A ROOF AREA AND THEN TO STAIRS ON |
| | THE OUTSIDE OF A BUILDING LEADING TO THE PUBLIC RIGHT |
| | OF WAY BELOW. |
| | PLEASE PROVIDE LIGHTING AS REQUIRED FOR THESE AREAS. |
| | PLEASE INDICATE NORMAL AND EMERGENCY FOR STAGE AREA AND |
| | STAIRS FROM THIS AREA. |
| | |
| | 9) NOTE: PLEASE SEE 620.23, 620.24 WHICH REQUIRES |
| | DEDICATED CIRCUITS FOR ELEVATOR LIGHTS/RECEPTACLES AND |
| | ELEVATOR EQUIPMENT ROOMS. PLEASE SEE THAT SOME OF THIS |
| | IS DONE; HOWEVER PLEASE SEE THAT THESE CIRCUITS MAY NOT |
| | FEED ANY OTHER AREAS. |
| | PLEASE ALSO INDICATE AN EMERGENCY LIGHT FIXTURE OF SOME |
| | KIND IN ELEVATOR EQUIPMENT ROOM. 700.12E, 700.16, LS |
| | 7.8, 7.9 AND STATE ELEVATOR CODE. |
| | |
| | 10) NOTE: PLEASE INDICATE HOW LIGHTING AND RECEPTACLE |
| | LOADS ARE DERIVED. PLEASE SEE 220.3, 220.10, 220.11, |
| | 220.13 ETC. |
| | |
| | 11) NOTE: PLEASE PLACE INFORMATION ON SYMBOL LEGEND FOR |
| | HORN AND STROBE DEVICES FOR FBC 2004 ADA LEVELS. |
| | 11-4.28.1, .2 AND .3(4). |
| | PLEASE SEE THERE ARE SEVERAL DIFFERENCES IN THE POWER |
| | PLANS COMPARED TO THE LIGHTING PLANS FOR DEVICE |
| | LOCATIONS. |
| | PLEASE ALSO SEE 11-4.28.1 AS THERE IS MANY LOCATIONS |
| | /ROOMS/AREAS WHICH DO NOT INDICATE ANY DEVICES. |
| | |
| | 12) NOTE: PLEASE CORRELATE ALL ARCHITECTURAL SHEETS |
| | WITH THE ELECTRICAL PLANS AS THERE ARE PANELS NOTED ON |
| | OTHER SHEETS WHICH DO NOT CORRELATE WITH ELECTRICAL FOR |
| | SIZES ETC. |
| | FBC 106.1.2, 106.3.5.1.2. |
| | |
| | 13) NOTE: PLEASE SEE TITLE BLOCKS WHICH CONTAINS |
| | *WHITE-OUT* OVER THE DRAFTING FIRM, PLEASE DO NOT USE |
| | WHITE OUT ON PLANS AND REMOVE THE TITLE BLOCKS WHEN |
| | REVISING PLANS. |
| | FS 471/481 |
| | |
| | ** PLEASE COMPLETE, CORRELATE AND SUBMIT PLANS FOR |
| | REVIEW. |
| | ** PLEASE KNOW AT THIS TIME, BASED ON MANY ITEMS WHICH |
| | CAN NOT BE REVIEWED FOR CODE COMPLIANCE, THERE MAY VERY |
| | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH ARE |
| | NOT ON THIS REVIEW AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |