| 2006-10-11 08:02:08 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. AN ARCHITECT OR ENGINEER IS REQUIRED TO DESIGN THE |
| | PLANS PER FS 481.229 |
| | |
| | 2. HOLD DATED 2-9-05 INDICATES THAT COMPLETE PLANS ARE |
| | REQUIRED. THIS IS A CHANGE OF OCCUPANCY, AND WORK WAS |
| | DONE WITH PERMITS. PLEASE SUBMIT FLOOR PLANS FOR BOTH |
| | FLOORS SHOWING FLOOR PLANS PRIOR TO CHANGES MADE WITH |
| | OUT PERMITS. SECTION 106.1.1. |
| | |
| | 3. PER FBC-2004 EXISTING BUILDING CODE, INDICATE LEVEL |
| | OF ALTERATION. CHAPTER 3. |
| | |
| | 4. SUBMIT CALCULATIONS FOR MINIMUM PLUMBING FACILITIES |
| | PER TABLES 1004.2 AND 403.1. |
| | |
| | 5. SEPARATE FACILITIES ARE REQUIRED FOR MEN AND WOMEN. |
| | NO WOMEN'S TOILET ROOM INDICATED. SECTION 403.2. |
| | |
| | 6. POTTY PARITY IS REQUIRED PER SECTION 403.1.1. THIS |
| | IS NOT INDICATED ON PLANS. |
| | |
| | 7. PER TABLE 403.1 AT LEAST ONE DRINKING FOUNTAIN IS |
| | REQUIRED. |
| | |
| | 8. SHT 3/5 HAS A NOTE THAT STATES, "PLUMBING PERMIT ON |
| | RECORD". SEE ATTACHED SHEET. NO PLUMBING PERMIT IS |
| | INDICATED ON RECORD. |
| | |
| | 9. SHT 3/5 MEW MEN'S TOILET ROOM STALL DOES NOT COMPLY |
| | WITH FIGURE 30E AS REQUIRED IN SECTION 11-4.17.3 |
| | EXCEPTION. ALSO A TURNING AREA IS REQUIRED IN THE |
| | TOILET ROOMS. PLEASE INDICATE ON PLANS. SECTION |
| | 11-4.22.3. |
| | |
| | 10. SHT 3/5 ELEVATIONS FOR WATER CLOSETS AND LAVS. SHOW |
| | THE FOLLOWING INFORMATION: |
| | FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT (SHOWN AS 20") |
| | C. 11-4.16.4 GRAB BARS (SHOW LENGTHS) |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAV'S |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 11. SUBMIT A DETAIL FOR THE URINAL SHOWING COMPLIANCE |
| | WITH 11-4.18 AND ALL SUBSECTIONS. |
| | |
| | 12. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS, AS WELL AS |
| | 11-4.1.3(10)(B) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING IF THE DRINKING FOUNTAIN |
| | IS NOT A HIGH/LOW UNIT. |
| | |
| | 13. SHT 3/5 PLUMBING SANITARY RISER DIAGRAM. URINALS |
| | ARE NOT VENTED. SECTION 901.2.1. |
| | |
| | 14. SUBMIT A WATER RISER DIAGRAM ISOMETRIC. SHOW ALL |
| | PIPE SIZES, VALVES, AND WATER HAMMER ARRESTORS AS |
| | REQUIRED BY SECTION 604.9. IF WATER HAMMER ARRESTORS |
| | ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE FIXTURE |
| | IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | REVIEW BY KEN STEVENS |