| 2006-10-24 11:03:23 | *****DENIED***** |
| | |
| | |
| | |
| | |
| | 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE |
| | PREVENTION CODE, 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 02.)STRUCTURES UNDERGOING CONSTRUTION, ALTERATION, |
| | AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.)AN ADDRESS IS REQUIRED ON THE BUILDING OF NO LESS |
| | THAN 6" IN HEIGHT AND 1" IN WIDTH.PLEASE INDICATE |
| | LOCATION OF THE ADDRESS ON THE APPROPIATE ELEVATION |
| | FRONTING BROADWAY AVENUE. |
| | |
| | 04.)WHAT IS THE OCCUPANCY CLASSIFICATION (I.E. |
| | ASEMBLY, BUSINESS, EDUCATIONAL) FOR THIS BUILDING? |
| | |
| | 05.)IS THE BUILDING PROTECTED BY FIRE PROTECTION |
| | SYSTEMS SUCH AS A FIRE SPRINKLER AND/OR FIRE ALARM |
| | SYSTEM? |
| | |
| | 06.)IN REFERENCE TO #5, IF THE SCOPE OF THE INTERIOR |
| | BUILDOUT REQUIRES MODIFICATION OF THE FIRE FIRE |
| | PROTECTION SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE |
| | SUBMITTED FOR REVIEW. |
| | |
| | 07.)IN ADDITION TO THE FIRE EXTINGUISHERS SHOWN ON |
| | THE LIFE SAFETY SHEETS, PLEASE INDICATE THE LOCATION OF |
| | EXIT LIGHTS, EMERGENCY LIGHTS, AND COMMON PATH TRAVEL |
| | DISTANCES TO THE EXITS. |
| | |
| | 08.)PANIC HARDWARE IS REQUIRED ON EXIT DOORS SERVING |
| | AN OCCUPANT LOAD GREATER THAN ONE HUNDRED. |
| | |
| | 09.)PLEASE INDICATE THE MINIMUM INTERIOR FINISH |
| | CLASSIFICATIONFOR WALLS AND CEILING IN TERMS OF CLASS |
| | A, B, OR C IN ACCORDANCE WITH NFPA 101, 10.2. |
| | |
| | 10.)CONSTRUTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |