| Date |
Text |
| 2006-09-24 00:00:00 | *** UNSAT 2ND REVIEW*** |
| | |
| | ** PLEASE SEE SAME COMMENTS FROM |
| | PREVIOUS REVIEW AND NEW COMMENTS. |
| | |
| | 1) NOTE:NO, SAME NOTE. |
| | PLEASE KNOW THIS ELECTRICAL SCOPE IS |
| | REQUIRED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT AND SHOW ALL |
| | ELECTRICAL REQUIRED FOR THE NEW PROPOSED |
| | ELEVATOR AND ELEVATOR MACHINE ROOM. |
| | NFPA-70 620., 620.23,620.24 ETC |
| | STATE ELEVATOR CODE. NFPA-101 ETC. |
| | |
| | ** PLEASE SEE NOTE ON PLANS MENTIONS |
| | SEPARATE ELECTRICAL PERMIT ALREADY |
| | APPLIED FOR, HOWEVER THE ELECTRICAL |
| | PERMIT DONE WAS FOR "DEMO ONLY " OF SOME |
| | EXISTING ELECTRICAL. |
| | |
| | ALL ELECTRICAL PLANS FOR THIS SCOPE |
| | SHALL BE SUBMITTED UNDER THIS PERMIT. |
| | |
| | 2) NOTE: NO, SAME NOTE, NO CHANGE MADE |
| | TO VALUE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE VALUE SHALL BE BASED |
| | ON ALL LABOUR AND MATERIALS EVEN OF ANY |
| | EQUIPMENT IS BEING OWNER SUPPLIED PER |
| | FBC108.3. |
| | PLEASEKNOW A VALUE MAY ALSO BE ASSESSEDD |
| | PER MARSHALL'S & SWIFT GUIDE AS ADOPTED |
| | BY THE FBC AND THIS OFFICE. |
| | |
| | 3) NOTE:NO, PLEASE SEE FS 481.223(1)(A) |
| | WHICH DEFINES WHO CAN PROVIDE |
| | ARCHITECTURAL DOCUMENTATION. |
| | COULD NOT LOCATE AN LICENSEURE |
| | INFORMATION FOR SAID COMPANY AS SHOWN ON |
| | PLANS. |
| | PLEASE SEE 481.203, 481.229 (1)(C), AS |
| | THIS SCOPE MUST BE DONE BY AN ARCHITECT |
| | OR ENGINEER AND A "DESIGN" OR "DRAFTING" |
| | FIRM MAY NOT DO PLANS AS SHOWN AND |
| | SUBMITTED. PLEASE KNOW, THIS WAS |
| | CONFIRMED WITH THE STATE'S LEGAL COUNSEL |
| | TO THE FLORIDA BOARD OF ARCHITECTS ON |
| | 9/22/06. |
| | PLEASE MAKE ADJUSTMENTS AND PLEASE KNOW, |
| | ONE SET OF PLANS ARE BEING RETAINED BY |
| | THIS OFFICE AT THE REQUEST OF THE |
| | BOARD'S LEGAL COUNSEL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ANY DOCUMENTATION |
| | SIGNED,DATED AND SEALED BY THE ENGINEER |
| | SHALL CONTAIN MIN TITLE BLOCKS AS |
| | REQUIRED UNDER FAC 61G15-23.002. PLEASE |
| | SEE THE ARCHITECTURAL TITLE BLOCK IS NOT |
| | RELEVANT FOR THE ENGINEER. |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE |
| | COMPLIANCE WITH REPSECT TO DESIGN |
| | PROFESSIONALS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |