| 2006-09-17 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SUBMIT AND SHOW ALL |
| | ELECTRICAL REQUIRED FOR THE NEW PROPOSED |
| | ELEVATOR AND ELEVATOR MACHINE ROOM. |
| | NFPA-70 620., 620.23,620.24 ETC |
| | STATE ELEVATOR CODE. NFPA-101 ETC. |
| | |
| | ** PLEASE SEE NOTE ON PLANS MENTIONS |
| | SEPARATE ELECTRICAL PERMIT ALREADY |
| | APPLIED FOR, HOWEVER THE ELECTRICAL |
| | PERMIT DONE WAS FOR "DEMO ONLY " OF SOME |
| | EXISTING ELECTRICAL. |
| | |
| | ALL ELECTRICAL PLANS FOR THIS SCOPE |
| | SHALL BE SUBMITTED UNDER THIS PERMIT. |
| | |
| | 2) NOTE: PLEASE SEE VALUE SAHLL BE BASED |
| | ON ALL LABOUR AND MATERIALS EVEN OF ANY |
| | EQUIPMENT IS BEING OWNER SUPPLIED PER |
| | FBC108.3. |
| | PLEASEKNOW A VALUE MAY ALOS BE ASSESSD |
| | PER MARSHALL'S & SWIFT GUIDE AS ADOPTED |
| | BY THE FBC AND THIS OFFICE. |
| | |
| | 3) NOTE: PLEASE SEE ANY DOCUMENTATION |
| | SIGNED,DATED AND SEALED BY THE ENGINEER |
| | SHALL CONTAIN MIN TITLE BLOCKS AS |
| | REQUIRED UNDER FAC 61G15-23.002. PLEASE |
| | SEE THE ARCHITECTURAL TITLE BLOCK IS NOT |
| | RELEVANT FOR THE ENGINEER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |