| 2006-09-14 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) PROVIDE BUILDING INFORMATION. SPECIFY |
| | THE TYPE OF CONSTRUCTION, BUILDING |
| | HEIGHT, NUMBER OF STORIES, WHETHER |
| | SPRINKLERED OR NOT. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) ENGINEER IS REQUIRED TO LEGIBLY |
| | INDICATE THEIR LICENSE NUMBER IN |
| | ADDITION TO NAME AND ADDRESS ON EACH |
| | SHEET OF THE PLANS. THIS INFORMATION IS |
| | ALSO REQUIRED ON SIGNED AND SEALED |
| | LETTERS. SEE FAC 61G15-23.002. |
| | |
| | 4) OVERHEAD DOOR WILL NOT COMPLY WITH |
| | ENERGY CODE REQUIREMENTS IF THE LOBBY IS CONDITIONED |
| | SPACE OR IS NOT SEPARATED |
| | FROM CONDITIONED SPACE. SEE FBC 13-403 |
| | AND 13-406. |
| | |
| | 5) THE PLANS MUST BE REVISED TO SHOW THE |
| | TYPE OF DOORS. A LETTER IS NOT |
| | SUFFICIENT. |
| | |
| | 6) SUBMIT PLANS THAT INDICATE THE |
| | EXISTING BUILDING WALL LOCATIONS PRIOR |
| | TO ANY DEMOLITION OR REMODELING. |
| | |
| | 7) SPECIFY HOW TERMITE PROTECTION WILL |
| | BE PROVIDED ON THE PLANS. FBC 1816.1 |
| | |
| | 8) EACH ENCLOSED ELEVATOR LOBBY AND EACH |
| | ELEVATOR MACHINE ROOM SHALL BE PROVIDED |
| | WITH AN APPROVED SMOKE DETECTOR LOCATED |
| | IN THE LOBBY CEILING IN ACCORDANCE WITH |
| | NFPA 72. SMOKE DETECTORS MAY BE |
| | INSTALLED IN ANY HOISTWAY, AND SHALL BE |
| | INSTALLED IN HOISTWAYS WHICH ARE |
| | SPRINKLERED. WHEN THE SMOKE DETECTOR IS |
| | ACTIVATED, ALL AFFECTED ELEVATORS SHALL |
| | OPERATE IN CONFORMANCE WITH NFPA 72, |
| | SECTION 3?9.3. FBC 3002.8 |
| | |
| | 9) THE ELEVATOR MUST COMPLY WITH |
| | ACCESSIBILITY REQUIREMENTS OF FBC 2007. |
| | |
| | 10) ELEVATOR MACHINE ROOMS AND MACHINERY |
| | SPACES SHALL BE ENCLOSED WITH |
| | CONSTRUCTION HAVING A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED RATING |
| | OF THE HOISTWAY ENCLOSURE SERVED BY THE |
| | MACHINERY. OPENINGS SHALL BE PROTECTED |
| | WITH ASSEMBLIES HAVING A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THAT REQUIRED FOR |
| | THE HOISTWAY ENCLOSURE DOORS. FBC 3006.4 |
| | |
| | 11) PROVIDE DETAILS AND THE TESTED FIRE |
| | ASSEMBLY TYPES AND FILE NUMBERS FOR ALL |
| | FIRE RATED ASSEMBLIES. |
| | |
| | 12)INDICATE ON THE PLANS THAT THE |
| | WALLS ADJACENT TO THE EGRESS STAIRS ARE |
| | FIRE RATED WALLS. THE DASHED LINE |
| | INDICATING RATED WALLS SHOULD CONTINUE |
| | AROUND THE STAIR SHAFT. |
| | |
| | 13) FBC 3202.2 ENCROACHMENTS INTO THE |
| | PUBLIC RIGHT-OF-WAY ABOVE GRADE AND |
| | BELOW 8 FEET (2438 MM) IN HEIGHT SHALL |
| | BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 3202.2.1 THROUGH 3202.2.3 . |
| | DOORS AND WINDOWS SHALL NOT OPEN OR |
| | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | SUBMIT A SITE PLAN SHOWING THE LOCATION |
| | OF THE PROPERTY LINES. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR |
| | EXISTING STOREFRONT DOORS THAT ARE TO BE RELOCATED. |
| | THEY MUST COMPLY WITH IMPACT |
| | AND WINDLOAD REQUIREMENTS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |