| Notes |
| Date |
Text |
| 2006-09-22 00:00:00 | | | | | | | DENIED/INCOMPLETE | | | | | | 1} PLEASE PROVIDE A DRAWING/CUT SHEET, | | | INDICATING WHAT TYPE OF RECEPTACLES | | | ENCLOSURE WILL BE USED AND HOW IT WILL | | | BE ATTACHED. | | | | | | 2} INDICATE CONDUIT AND RACEWAY SYSTEM | | | WILL BE USED FOR THE CONDUCTORS. | | | | | | 3} THE REQUIRED WALL MOUNTED SWITCH FOR | | | LIGHTING PER 210.70(A)(1) IS NOT SHOWN | | | ON THE PLAN. INDICATE THE RACEWAY SYSTEM | | | FROM SWITCH TO FIXTURE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561) 805-6718 | | | |
|