Plan Review Notes
Plan Review Notes For Permit 06090181
Permit Number 06090181
Review Stop B
Sequence Number 3
Notes
Date Text
2006-12-20 16:58:24REVISION DENIED BY BUILDING
  
 1) THE ENGINEERING FOR THE EXTERIOR WINDOW REPAIR IS
 REQUIRED TO REFERENCE THE APPLICABLE BUILDING CODE
 EDITION (2004 FLORIDA BUILDING CODE) AND THE WIND
 DESIGN DATA. SEE FBC 1603..1.4.
  
 2)IN ORDER TO BE SUBMITTED AS A REVISION TO THIS
 PERMIT THE ENGINEERING IS REQUIRED TO BE SIGNED AND
 SEALED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 WILFREDO F. PEREZ AR0013418.
  
 3)ALTERNATELY, A SEPARATE PERMIT WITH ADDITIONAL FEES
 CAN BE APPLIED FOR WITH THE NEW ENGINEERS CORRECTED
 DOCUMENTS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714