Plan Review Notes
Plan Review Notes For Permit 06090180
Permit Number 06090180
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-17 00:00:00 
  
 DENIED
  
 1) CIY OF WEST PALM BEACH REQUIRES 2
 COPIES OF THE FLORIDA STATE PRODUCT
 APPROVAL COVER SHEETS AND THE ASSOCIATED
 DRAWINGS, EVALUATION REPORTS OR
 MIAMI-DADE NOA THAT WAS USED FOR THE
 STATE APPROVAL.
 PROVIDE THE SAME COVERS AS THE ONES
 SUPPLIED WITH THE SIDING PRODUCT
 APPROVALS
  
 2) LAYOUT PLAN SHOWS DH WINDOWS AND
 PRODUCT APPROVAL SUBMITTED IS FOR SH
 PLEASE CORRECT
  
 3) PER CITY OF WEST PALM IMPACT
 PROTECTION MEMO(SEE ENCLOSED) PLEASE
 SUBMIT A KEY PLAN FOR THE SHUTTERS AND
 AN INSTALLATION SCHEDULE. ALSO MARK THE
 NOA DRAWINGS WITH THE APPICIBLE MOUNTING
 METHOD, ANCHOR TYPE, ETC THAT WILL BE
 USED
  
 4) ONLY 1 COPY OF SH WINDOW WAS
 SUBMITTED
  
 5) DRAWING SHOWS LIVINGROOM FIXED AND
 SH/DH TOGETHER, ALSO 2 SH/DH IN THE
 MASTER BEDROOM ARE THESE MULLED TOGETHER
 IF SO PLEASE SUBMIT PRODUCT APPRVALS FOR
 MULLIONS
  
 6) PLEASE VERIFY THAT NO WINDOW OPENINGS
 ARE TO BE RESIZED IN THE BEDROOMS IF SO
 THEY ARE REQUIRED TO MEET CODE FOR
 EMERGENCY EGRESS
  
 EMERGENCY EGRESS PER R310 FBC:
 MIN. NET CLEAR OPENING OF 5 SQ.FT. ON
 GRADE FLOOR. MIN. NET CLEAR OPENING ALL
 OTHER FLOORS OF 5.7 SQ.FT. IN BOTH CASES
 THE MIN.NET CLEAR HEIGHT SHALL BE 24"
 AND THE NET CLEAR WIDTH SHALL BE 20"
  
 REPLACEMENT WINDOWS THAT MEET OR ARE
 GREATER THAN THESE REQUIREMENTS SHALL BE
 ALLOWED A MAX. 5% REDUCTION IN CLEAR
 OPENING DIMENSIONS PER 505 EXISTING FBC
  
 REPLACEMENT OF WINDOWS NEED NOT MEET
 THESE REQUIREMENTS IF THERE IS NO
 REDUCTION IN THE NET CLEAR OPENING SIZE
 BETWEEN THE EXISTING AND NEW WINDOWS
  
 7) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716
  
  
  
  
  
  
  
  
  
  