| 2007-05-15 09:12:36 | --------------DENIED---------------- |
| | |
| | FBC 2004 CODE FAMILY W/2005 REVISIONS |
| | FBC 2004 CH.1 AS AMENDED BY THE CITY OF WEST PALM |
| | BEACH |
| | |
| | 1. WHAT IS THE SIZE OF THE FLEX DUCT FEEDING SUPPLY |
| | DISTRIBUTION BOX IN ROOM 104? |
| | |
| | 2. WHAT IS THE CFM OF THE 6" SUPPLY FLEX IN CORR. 105? |
| | |
| | 3. ROOM 113 SHOWS 8" FLEX SUPPLY AND RETURN WITH 320 |
| | AND 290 CFM RESPECTIVELY. THESE ARE OUTSIDE THE RANGES |
| | OF THE FLEX SCHEDULES FOR 8" ON PG M6.1. PLEASE |
| | CLARIFY. |
| | |
| | 4. ROOMS 107,109,115 ALSO SHOW FLEX DUCTS WITH CFM'S |
| | OUTSIDE OF THE RANGES ON THE M6.1 SCHEDULE. |
| | |
| | 5. RTU-3: 14" FLEX ATTACHED TO R/A RISER IS CARRYING |
| | 1230 CFM. SCHEDULE STATES A MAX. 700 CFM FOR 14" R/A |
| | FLEX. WHICH IS CORRECT? PLEASE CLARIFY. |
| | |
| | 6. RTU-4: WHAT IS THE SIZE OF THE SUPPLY FLEX FEEDING |
| | DISTRIBUTION BOX FOR ROOMS 149,153,155? |
| | |
| | 7. RTU-4: EQUIPMENT SCHEDULE CALLS FOR 2600 CFM. FLOOR |
| | PLAN SHOWS 2320 CFM. WHICH ONE IS CORRECT? ALSO, THERE |
| | ARE ONLY 755 CFM TOTAL RETURN AIR FOR THIS SYSTEM, |
| | LEAVING SOME AREAS WITHOUT BALANCED RETURN AS REQUIRED |
| | BY FBC,M 601.4. |
| | |
| | 8. ROOM 118 SHOWS 8" SUPPLY FLEX AT 260 CFM, OUTSIDE |
| | THE RANGE AS SHOWN ON FLEX SCHEDULE. PLEASE CLARIFY. |
| | |
| | 9. ROOM 152 SHOWS 6" R/A FLEX AT 120 CFM, OUTSIDE THE |
| | RANGE AS SHOWN ON FLEX SCHEDULE. PLEASE CLARIFY. |
| | |
| | 10. CORR. 140 SHOWS "AA" GRILL FOR 290 CFM WITH NO DUCT |
| | OR GRILL SHOWN IN CEILING. IS THIS TO BE THROUGH THE |
| | DOOR INTO ROOM 141? IF SO, HOW WILL 290 CFM BE DRAWN |
| | THROUGH THE DOOR? THERE IS ONLY 115 CFM OF EXHAUST IN |
| | THIS SPACE. PLEASE CLARIFY. |
| | |
| | 11. ROOM 132 SHOWS "AA" GRILL FOR 240 CFM. NO GRILL IS |
| | SHOWN IN CEILING AND NO DUCT IS SHOWN. PLEASE CLARIFY. |
| | |
| | 12. RTU-5: SCHEDULE SHOWS 1780 CFM SUPPLY. FLOOR PLAN |
| | SHOWS 2400 CFM SUPPLY WITH 2380 CFM RETURN. WHICH IS |
| | CORRECT? ALSO, HOW WILL 200 CFM OUTDOOR AIR BE |
| | INTRODUCED IF THE UNIT RETURNS ALL BUT 20 CFM OF INDOOR |
| | AIR? |
| | |
| | 13. THE AMOUNT OF SUPPLY AIR (INCLUDING OUTDOOR AIR) |
| | SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN |
| | AND EXHAUST AIR PER FBC,M 403.1. |
| | BASED ON TOTAL CFM AS SHOWN ON FLOOR PLAN: |
| | |
| | SUPPLY: 11,040 CFM |
| | RETURN: 8,755 CFM |
| | EXHAUST: 325 CFM |
| | |
| | RETURN PLUS EXHAUST IS 9,080 CFM WHICH IS 1960 CFM LESS |
| | THAN THE SUPPLY. RETURN PLUS EXHAUST SHOULD APPROX. |
| | EQUAL 11,040 CFM, WITH THE EXHAUST BEING APPROX. EQUAL |
| | TO THE 1170 CFM OF OUTDOOR AIR SHOWN ON SCHEDULE TO |
| | ACHIEVE THE VENTILATION RATES REQUIRED BY FBC,M 403.3. |
| | NOTE: THE ABOVE R/A TOTAL DOES NOT INCLUDE THE RETURNS |
| | QUESTIONED IN COMMENTS 10 AND 11, BUT THIS IS NOT |
| | ENOUGH TO PUT THE SYSTEM IN BALANCE. |
| | |