| 2006-09-18 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE PROIVDE THE YEARS FOR |
| | THE CODE BEING REFERENCED WHICH ARE |
| | CURRENTLY IN EFFECT AND RELEVANT TO |
| | DESIGN. |
| | NFPA-70 (NEC) 2002, NFPA-72 2002, |
| | NFPA-101 2003 AND THE 2004 FBC ON |
| | ELECTRICAL PLANS. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 2) NOTE: PLEASE VERIFY THE LOCATIONS OF |
| | THE EM LTS AND NIGHT LTS. |
| | PLEASE SEE THE SYMBOL BEING USED FOR THE |
| | NL'S APPEAR TO BE ON SOME FIXTURES WHICH |
| | ARE NOT THE EM LTS/W/ BATTERY BACK UP. |
| | IF THE EM LTS ARE NOT ON THE NL CIRCUIT, |
| | WIRED AHEAD OF ANY SWITCHABLE MEANS, |
| | THIS WOULD CAUSE EACH OF THESE TO BE RUN |
| | DOWN EACH NIGHT. PLEASE SEE THAT IT |
| | APPEARS IT MAY BE A MISPRINT FOR THE |
| | LOCATION OF THESE ON PLANS.?? |
| | 700.12E. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2, AND .1.3. |
| | PLEASE SEE SOME NOTES ARE MENTIONED FOR |
| | SOME SORT OF LIGHTING CONTROL, HOWEVER |
| | ONLY IT SEEMS FOR COMMON AREAS? |
| | PLEASE SEE .1.3, FOR ALL SEPARATE AREAS, |
| | WITH FLR TO CEILING HEIGHT PARTITIONS. |
| | PLEASE SUBMIT AND SHOW THE ENTIRE SYSTEM |
| | BEING INSTALLED AND PROPOSED. PLEASE |
| | INCLUDE ALL LOCATIONS FOR OVER-RIDE |
| | DEVICES AS REQUIRED INCLUDING INGRESS/ |
| | EGRESS INTO SPACE, SO THE OCCUPANT MAY |
| | VISUALLY SEE LIGHTING BEING CONTROLLED. |
| | PLEASE SUBMIT THE SCHEDULING TO TIME OF OPERATION. |
| | PLEASE INDICATE TH MAXIMUM OF THE TIMES |
| | ALLOWED FOR EACH TYPE OF OVER-RIDE |
| | DEVICE WHICH MAY BE CHOOSEN. (TIMER |
| | TYPE, 4HRS MAX, SENSOR TYPE 30 MINS MAX) |
| | PLEASE BE SURE TO UPDATE THE SYMBOL |
| | LEGEND FOR DEVICES CHOSEN. |
| | PLEASE PROVIDE LIGHTING POWER DENSITIES, |
| | PER 13-415.1.AB.1, 415.2.C.1, 415.2.B.1 |
| | ETC. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AT 125%. |
| | 215.3,230.42 |
| | |
| | 5) NOTE: PLEASE SEE PANEL SCHEDULE |
| | MENTIONS THE FACP IS GOING TO HAVEA |
| | RECEPT AT THIS LOCATION.PLEASE VERIFY |
| | THE RECEPT AND WHERE IT WILL BE LCOATED. |
| | PLEASE SEE ELECTRICAL PLANS INDICATE THE |
| | CIRCUIT LOCATION, HOWEVER THE FACP IS |
| | NOT SHOWN. PLEASE SEE THE FOLLOWING TEXT |
| | FROM NFPA-72 |
| | 4.4.1.4.2.1THE DEDICATED BRANCH |
| | CIRCUIT(S) AND CONNECTIONS SHALL BE |
| | MECHANICALLY PROTECTED. |
| | 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS |
| | SHALL HAVE A RED MARKING, SHALL BE |
| | ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, |
| | AND SHALL BE IDENTIFIED AS "FIRE ALARM |
| | CIRCUIT." |
| | 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING |
| | MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM |
| | CONTROL |
| | UNIT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2006-09-17 00:00:00 | IN ELEC FOR REVIEW. |