| 2006-10-05 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SPECIFY THE LEVEL OF ALTERATION AS |
| | SPECIFIED IN CHAPTER 3 OF THE 2004 FBC |
| | EXISTING BUILDING CODE. |
| | |
| | 3) SPECIFY THE TYPE OF CONSTRUCTION FOR |
| | THE BUILDING. SEE 2004 FBC 602 AND |
| | TABLES 601 AND 602. |
| | |
| | 4) THERE ARE TWO DETAIL ELEVENS ON SHEET |
| | A5.0. PLEASE CORRECT. |
| | |
| | 5) SPECIFY THE INSULATION AND REQUIRED |
| | FIRE RESISTANCE RATING FOR THE NEW |
| | EXTERIOR MASONRY WALL SHOWN IN DETAIL |
| | 11/A5.0 |
| | |
| | 6) 2004 FBC 1014.2.1 TWO EXITS OR EXIT |
| | ACCESS DOORWAYS. |
| | WHERE TWO EXITS OR EXIT ACCESS DOORWAYS |
| | ARE REQUIRED FROM ANY PORTION OF THE |
| | EXIT ACCESS, THE EXIT DOORS OR EXIT |
| | ACCESS DOORWAYS SHALL BE PLACED A |
| | DISTANCE APART EQUAL TO NOT LESS THAN |
| | ONE-HALF OF THE LENGTH OF THE MAXIMUM |
| | OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED MEASURED |
| | IN A STRAIGHT LINE BETWEEN EXIT DOORS OR |
| | EXIT ACCESS DOORWAYS. INTERLOCKING OR |
| | SCISSOR STAIRS SHALL BE COUNTED AS ONE |
| | EXIT STAIRWAY. |
| | EXCEPTIONS: |
| | 1.WHERE EXIT ENCLOSURES ARE |
| | PROVIDED AS A PORTION OF THE REQUIRED |
| | EXIT AND ARE INTERCONNECTED BY A 1-HOUR |
| | FIRE-RESISTANCE-RATED CORRIDOR |
| | CONFORMING TO THE REQUIREMENTS OF |
| | SECTION 1016 , THE REQUIRED EXIT |
| | SEPARATION SHALL BE MEASURED ALONG THE |
| | SHORTEST DIRECT LINE OF TRAVEL WITHIN |
| | THE CORRIDOR. |
| | 2.WHERE A BUILDING IS EQUIPPED |
| | THROUGHOUT WITH AN AUTOMATIC SPRINKLER |
| | SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2 , THE SEPARATION |
| | DISTANCE OF THE EXIT DOORS OR EXIT |
| | ACCESS DOORWAYS SHALL NOT BE LESS THAN |
| | ONE-THIRD OF THE LENGTH OF THE MAXIMUM |
| | OVERALL DIAGONAL DIMENSION OF THE AREA |
| | SERVED. |
| | THE EXITS TO THIS SPACE DO NOT COMPLY. |
| | PLEASE REVISE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |