Plan Review Notes
Plan Review Notes For Permit 06090154
Permit Number 06090154
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-25 00:00:00*****UNSAT*****
  
  
  
  
  
  
 1.) NOTICE OF COMMENCEMENT IS EXPIRED,
 OVER 90 DAYS WITHOUT COMMENCING WORK.
 F.S. 713.13(2)IF FURTHER EXPLANATION
 IS NEEDED, CALL SAMANTHA HILL AT
 805-6724.
  
  
 2.) FIRE SPRINKLER SYSTEM TO BE
 MONITORED AND/OR TIED INTO FIRE ALARM
 SYSTEM.
  
 3.) FIRE DEPARTMENT CONNECTIONS SHALL BE
 TWO OR MORE 2.5" CONNECTIONS OR ONE
 LARGE DIAMETER (4" OR LARGER)
 CONNECTION.
  
 4.) IF FIRE DEPARTMENT CONNECTION IS NOT
 READILY VISIBLE, POST SIGN WITH 6-INCH
 LETTERS (FDC) AND 2-INCH WORDS.
  
 5.) PLEASE EXPLAIN THE ABSENCE OF
 HYDRAULIC CALCULATIONS FOR THE 3RD AND
 4TH FLOOR.
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722