| Plan Review Notes For Permit 06090154 |
| Permit Number |
06090154 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-25 00:00:00 | *****UNSAT***** | | | | | | | | | | | | | | | | | | | | | 1.) NOTICE OF COMMENCEMENT IS EXPIRED, | | | OVER 90 DAYS WITHOUT COMMENCING WORK. | | | F.S. 713.13(2)IF FURTHER EXPLANATION | | | IS NEEDED, CALL SAMANTHA HILL AT | | | 805-6724. | | | | | | | | | 2.) FIRE SPRINKLER SYSTEM TO BE | | | MONITORED AND/OR TIED INTO FIRE ALARM | | | SYSTEM. | | | | | | 3.) FIRE DEPARTMENT CONNECTIONS SHALL BE | | | TWO OR MORE 2.5" CONNECTIONS OR ONE | | | LARGE DIAMETER (4" OR LARGER) | | | CONNECTION. | | | | | | 4.) IF FIRE DEPARTMENT CONNECTION IS NOT | | | READILY VISIBLE, POST SIGN WITH 6-INCH | | | LETTERS (FDC) AND 2-INCH WORDS. | | | | | | 5.) PLEASE EXPLAIN THE ABSENCE OF | | | HYDRAULIC CALCULATIONS FOR THE 3RD AND | | | 4TH FLOOR. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|