| Date |
Text |
| 2006-11-17 06:45:28 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUES |
| | |
| | *******FROM 1ST REVIEW******* |
| | |
| | 1. ALL SHEETS. THE ARCHITECTS TITLE |
| | BLOCK DOES NOT REFLECT THE ADDRESS FOUND |
| | ON THE DBPR WEBSITE. FAC 61G1-16.004(1) |
| | AND FS 481.2055. (SEE ATTACHED SHEET). ****RESPONSE |
| | NOTED. SUBMIT A LETTER FROM DBPR INDICATING APPROVAL OF |
| | THIS TEMPORY ARRANGEMENT. I DO NOT HAVE THE AUTHORITY |
| | TO WAIVE THIS REQUIREMENT OF THE FLORIDA ADMINISTRATIVE |
| | CODE/FLORIDA STATUTES. |
| | |
| | 2. ROUTE PLANS TO DBPR HOTEL AND |
| | RESTURANT DIVISION FOR REVIEW. MINIMUM 2 |
| | SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" |
| | REQUIRED FOR REVIEW. |
| | SECTION 102.2.1. |
| | ****RESPONSE NOTED. THIS IS REQUIRED FOR THE PLAN |
| | REVIEW AND SHALL BE REVIEWED BY DBPR, PLANS STAMPED AND |
| | WORKSHEETS ATTACHED AS REQUESTED. |
| | |
| | 3. A GREASE INTERCEPTOR MAY BE REQUIRED. |
| | PLEASE CONTACT LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE (561) 822-2271, |
| | FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. WASTE ORD. 3434. |
| | ****RESPONSE NOTED BUT NOT ACCEPTABLE. PLEASE CONTACT |
| | ENVIRONMENTAL COMPLIANCE. GREASE TRAP INSIDE NOT |
| | APPROVED. PER MUNICIPAL CODE A MINIMUM 750 GAL.GREASE |
| | INTERCEPTOR IS REQUIRED. |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT P-1 WATER FILTERS SHALL BE |
| | COMPLIANT WITH NSF-42. SUBMIT MANUF. |
| | SPECIFICATION SHEETS. |
| | ****RESPONSE NOTED. MANUFACTURE CUT SHEET INDICATED WAS |
| | NOT FOUND IN RESUBMITTAL. |
| | |
| | 8. SHTS A-6 & P-1. SHT A-6 INDICATES A |
| | NEW OVEN, AND SHT P-1 INDICATES A FRYER |
| | AND THE OVEN AS RECONNECTING (GAS SIZE |
| | AND CAPACITY SAME EXISTING). A GAS |
| | PERMIT WILL BE REQUIRED AND THE |
| | FOLLOWING INFORMATION WILL BE REQUIRED |
| | TO VERIFY COMPLIANCE WITH THE GAS CODE: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B" |
| | TO "D" IS NOT INDICATED |
| | |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT. |
| | ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C", |
| | AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B" |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES |
| | 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004 |
| | FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5 |
| | PSI, NOT 1 PSI OR LESS. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR |
| | ALL NEW EQUIPMENT). |
| | ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE |
| | REQUIRED FOR PLAN REVIEW. |
| | |
| | H. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |