| 2006-11-27 17:44:01 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEW |
| | |
| | 1. SHTS A-6 & P-1. SHT A-6 INDICATES A |
| | NEW OVEN, AND SHT P-1 INDICATES A FRYER |
| | AND THE OVEN AS RECONNECTING (GAS SIZE |
| | AND CAPACITY SAME EXISTING). A GAS |
| | PERMIT WILL BE REQUIRED AND THE |
| | FOLLOWING INFORMATION WILL BE REQUIRED |
| | TO VERIFY COMPLIANCE WITH THE GAS CODE: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B" |
| | TO "D" IS NOT INDICATED |
| | |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT. |
| | ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C", |
| | AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B" |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES |
| | 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004 |
| | FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5 |
| | PSI, NOT 1 PSI OR LESS. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR |
| | ALL NEW EQUIPMENT). |
| | ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE |
| | REQUIRED FOR PLAN REVIEW. |
| | |
| | H. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |