| Date |
Text |
| 2006-09-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUES |
| | |
| | 1. ALL SHEETS. THE ARCHITECTS TITLE |
| | BLOCK DOES NOT REFLECT THE ADDRESS FOUND |
| | ON THE DBPR WEBSITE. FAC 61G1-16.004(1) |
| | AND FS 481.2055. (SEE ATTACHED SHEET). |
| | |
| | 2. ROUTE PLANS TO DBPR HOTEL AND |
| | RESTURANT DIVISION FOR REVIEW. MINIMUM 2 |
| | SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" |
| | REQUIRED FOR REVIEW. |
| | SECTION 102.2.1. |
| | |
| | 3. A GREASE INTERCEPTOR MAY BE REQUIRED. |
| | PLEASE CONTACT LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE (561) 822-2271, |
| | FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. WASTE ORD. 3434. |
| | |
| | 4. SHT A-5 PLEASE SHOW COMPLIANCE WITH |
| | THE FOLLOWING: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 5. SHT P-1 ALL EQUIPMENT & FIXTURES |
| | UTILIZED FOR STORAGE, PREPARATION AND |
| | HANDLING OF FOOD SHALL DISCHARGE THROUGH |
| | AN INDIRECT WASTE PIPE BY MEANS OF AN |
| | AIR GAP. SECTION 802.1.1. - FLOOR SINKS |
| | ARE REQUIRED PER SECTION 802.3. |
| | |
| | 6. SHT P-1 PLUMBING NOTES #13 AIR |
| | CHAMBERS ARE NOT APPROVED. WATER HAMMER |
| | ARRESTORS REQUIRED AT QUICK CLOSING |
| | VALVES SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE", (NOT |
| | IN THE CEILING), PER PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. (ICE |
| | MAKERS, DISHWASHERS, ETC). |
| | |
| | 7. SHT P-1 WATER FILTERS SHALL BE |
| | COMPLIANT WITH NSF-42. SUBMIT MANUF. |
| | SPECIFICATION SHEETS. |
| | |
| | 8. SHTS A-6 & P-1. SHT A-6 INDICATES A |
| | NEW OVEN, AND SHT P-1 INDICATES A FRYER |
| | AND THE OVEN AS RECONNECTING (GAS SIZE |
| | AND CAPACITY SAME EXISTING). A GAS |
| | PERMIT WILL BE REQUIRED AND THE |
| | FOLLOWING INFORMATION WILL BE REQUIRED |
| | TO VERIFY COMPLIANCE WITH THE GAS CODE: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR |
| | ALL NEW EQUIPMENT). |
| | |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. (INDICATED |
| | AS EXISTING RELOCATING). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |