| Date |
Text |
| 2006-10-13 07:57:06 | DENIED: |
| | PLEASE CLARIFY THE FOLLOWING: |
| | 1.PLAN SHEET A-1 INDICATES WEST WALL IS INDICATED AS |
| | A EXISTING TENANT DEMISING WALL.IS THIS AN EXTERIOR |
| | WALL OR IS THIS INTERIOR TO THE TENANT SPACE.PLEASE |
| | CLARIFY IF THIS WILL BE SEPARATED OR PROTECTED BY AN |
| | ENCLOSURE OR SHAFT? |
| | |
| | 2.PLAN SHEET M-1 DUCT MISSING FIRE DAMPER FROM |
| | 20"X48" R/A DUCT PENETRATING TENANT DEMISING WALL. |
| | |
| | 3.PLEASE PROVIDE CLEARANCES FROM THE GREASE DUCT TO |
| | COMBUSTIBLES.SHOW COMPLIANCE WITH 2004 FMC 506.3.6. |
| | |
| | 4.PLAN SHEET M-1 INDICATES EF-2 SERVES A COOK LINE |
| | HOOD TERMINATING ON THE ROOF.THIS IS NOT SHOWN ON |
| | PLAN SHEET M-1.2. |
| | |
| | 5.PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE |
| | HOOD & GREASE DUCT: |
| | A) TYPE I OR TYPE II HOOD |
| | B) INDICATE HOOD & DUCT MATERIAL AND GAUGE 2004 |
| | FMC 507.4, 507.5, 506.3.1.1 & 506.4. |
| | C) INDCIATE DUCT SIZE AND LAYOUT |
| | D) AIR VELOCITY THROUGH THE GREASE DUCT SHALL |
| | COMPLY WITH 2004 FMC 506.3.4 |
| | |
| | 6.PLAN SHEET M-1.2 APPEARS TO HAVE A WALL THAT |
| | TERMINATES ABOVE THE ROOF THAT SEPARATES RTU-1 & EF-1. |
| | PER 2004 FMC 306.5, ACCESS SHALL NOT REQUIRE CLIMBING |
| | OVER OBSTRUCTIONS GREATER THAN 30 INCHES.PLEASE NOTE, |
| | SHOULD ROOF HAVE A SLOPE GREATER THAN 4/14 PITCH SHOW |
| | COMPLIANCE WITH 306.5 ITEMS 1 THROUGH 7. |
| | |
| | 7.PLEASE INDICATE ACCESS TO ROOF. |
| | |
| | 8.PLEASE CLARIFY WHAT EQUIPMENTTHE20"X48" RETURN |
| | AIR DUCT & 20"X32" SUPPLY DUCT TERMINATING ON THE ROOF |
| | GO TO (RTU-1?) |
| | |
| | 9.ADDITIONAL PERMITS REQUIRED FOR HOOD, FIRE |
| | SUPPRESSION, & WALK-IN COOLER.PLEASE PROVIDE PLANS |
| | AND MANUFACTURER'S SUBMITTAL DATA WITH PERMIT |
| | APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS |
| | AT (561)805-6719 OR E-MAIL [email protected]. |