| 2006-10-12 11:45:03 | *****DENIED***** |
| | |
| | |
| | |
| | |
| | 1.)CONSTRUCTION, ALTERATION, ANDDEMOLITION |
| | OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING |
| | AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B. |
| | |
| | 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 4.)THE SCOPE OF THE INTERIOR BUILDOUT REQUIRING |
| | MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER |
| | SYSTEM, SEPARATE PERMIT AND PLANS ARE REQUIRED. |
| | |
| | 5.)INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS |
| | AND EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| | |
| | 6.)ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY |
| | THE ADDRESS FOR THIS STRUCTURE.AS PER WEST PALM BEACH |
| | CODE, THE CHARACTERS (NUMBERS AND/OR LETTERS) SHALL BE |
| | NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING |
| | WITH THE BACKGROUND.IF USED, HURRICANE SHUTTERS SHALL |
| | NOT COVER OR CONCEAL ADDRESS. |
| | |
| | 7.)ADDITIONAL MECHANICAL PERMITS AND PLANS ARE |
| | REQUIRED FOR HOOD/SUPPRESSION SYSTEM(S). |
| | |
| | 8.)ON SHEET M-3 HOOD SYSTEM NOTE #1, REFERENCES SHALL |
| | BE MADE TO NFPA 96, 2004 EDITION. |
| | |
| | 9.)AS PER WPBFR, DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL FIRE ALARM. |
| | |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |