| 2006-09-19 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE SERVICE IS BEING |
| | SHOWN TO A 350A CAPABILITY , HOWEVER |
| | RISER SHOWS A 200A METER CAN BEING |
| | TAPPED. |
| | PLEASE SEE NOTES ON LOAD CALCS, AS LOADS |
| | EXCEED RATINGS OF EQUIPMENT AS SHOWN. |
| | 240.4,310.16,230.70 ETC |
| | |
| | 2) NOTE: PLEASE INCLUDE CONDUCTORS FROM |
| | METER TO GUTTER ANF FROM GUUTER TO NEW |
| | MAIN. |
| | 240.310.16 ETC |
| | |
| | 3) NOTE: PLEASE SHOW LOAD ON EXISTING |
| | GUTEER, SIZE AND NEW LOADS BEIGN ADDED. |
| | 220, 215. ETC. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE SEE LOAD CALCS MENTIONS |
| | TWO PANEL "B" 'S? |
| | PLEASE CLARIFY. |
| | 106.1.2 FBC. |
| | |
| | 5) NOTE: PLEASE INDICATE NEW OR EXISTING |
| | SIGN CIRCUIT(S) PER 600.5 |
| | |
| | 6) NOTE: PLEASE INDICATE NEW OR EXISTIGN |
| | RECEPTS ABOVE WINDOWS. (EVERY 12' OR |
| | FRACTION THEROF. |
| | 210.62, 220.12 |
| | |
| | 7) NOTE: PLEASE SEE THIS SERVICE IS |
| | BEING SHOWN FOR ONE TENANT, YET IT IS |
| | ALSO BEING SHOWN FOR FEEDING |
| | "COURTYARD"?? |
| | PLEASE VERIFY AS THE CODE DOES NOT |
| | PERMIT COMMON AREA LIGHTING ETC BEING |
| | CONTROLLED OR FED FROM A TENANT |
| | OCCUPANCY. |
| | 210.25, 240.24 |
| | |
| | 8) NOTE: PLEASE CLARIFY SHUNT BRKR FOR |
| | ANY HOOD POWER/ LTS. NFPA-96 |
| | |
| | 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR |
| | AUTOMATED LIGHTING CONTROLLED REQUIRED. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE PROVIDE SCHEDULING, TIMERS, |
| | OVER-RIDES AND TYPES OF DEVICES. PLEASE |
| | SHOW ALL CONTROL/OVER RIDE LOCATIONS. |
| | PLEASE SEE ALL SEPARATE SPACES WITH FLR |
| | TO CEILING HEIGHT PARTITIONS, WITH |
| | CONTROLS. |
| | PLEASE PROVIDE ENERGY CALCULATIONS AS |
| | REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1, |
| | 415.2.C. |
| | |
| | PLEASE SEE THERE ARE SWITCHES BEING |
| | SHOWN ON PLANS WHICH DO NOT INDICATE |
| | CONTROL OF ANY PARTICULAR ITEM.? |
| | |
| | 10) NOTE: PLEASE SHOW NEW OR EXISTING |
| | GFI RECEPT FOR ROOF TOP EQUIPMENT PER 210.8,210.63 |
| | |
| | 11) NOTE: PLEASE INDICATE THE AIC |
| | RATINGS FOR ALL NEW SERVICE |
| | MAINS/EQUIPMENT. |
| | 110.9 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |