| Date |
Text |
| 2006-10-05 00:00:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS, |
| | FS713.13. |
| | |
| | 2.)SHEET A.0 DECLARES A2 OCCUPANCY, |
| | EXIT REQUIREMENTS ARE FOR MERCANTILE, |
| | PLEASE REVISE. |
| | |
| | 3.)DELCARE LEVEL OF ALTERATION FBC EB |
| | 3 AND INCLUDE FBC EB IN GOVERNING CODE. |
| | |
| | 4.)WHAT IS THE CURRENT OCCUPANCY?IF |
| | THIS IS A CHANGE OF OCCUPANCY, INDICATE |
| | ON THE PLAN. |
| | |
| | 5.)PROVIDE ADDITIONAL INFORMATION IN |
| | REGARDS TO THE EXISTING BUILDING; TOTAL |
| | SF AREA, HEIGHT.CEILING HEIGHT IS |
| | SHOWN BUT PLEASE PROVIDE BUILDING |
| | HEIGHT. |
| | |
| | 6.)SHOW MANEUVERING CLEARANCE, PULL |
| | SIDE, FOR DOORS 03, 04, 05 FBC11-4.13.6, |
| | FIGURE 11-25. |
| | |
| | 7.)SEE FBC11-7.2, SERVICE COUNTER |
| | REQUIREMENT OF 36IN HEIGHT FOR A MINIMUM |
| | LENGTH OF 36IN, 40IN HEIGHT SHOWN. |
| | |
| | 8.)THE PLAN STATES THAT SF AREA IS |
| | 2853, ENERGY CALCS STATE 2250.REVISE. |
| | |
| | 9.)THE ENERGY CALCS DECLARE PALM BEACH |
| | COUNTY AS JURISDICTION; CORRECT |
| | JURISDICTION IS CITY OF WEST PALM BEACH, |
| | 604700. |
| | |