| Date |
Text |
| 2006-09-21 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 2) THE DESIGN LOADS AND OTHER |
| | INFORMATION PERTINENT TO THE STRUCTURAL |
| | DESIGN REQUIRED BY SECTIONS 1603.1.1 |
| | THROUGH 1603.1.8 SHALL BE CLEARLY |
| | INDICATED ON THE CONSTRUCTION DOCUMENTS |
| | FOR PARTS OF THE BUILDING OR STRUCTURE. |
| | |
| | 3) PROVIDE WIND DESIGN DATA ON DRAWINGS |
| | PER 1603.1.4 FBC. THE 2004 FBC NOW |
| | REFERENCES ASCE 7-02 |
| | |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO |
| | WIND LOADS SHALL BE SHOWN, REGARDLESS OF |
| | WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL-FORCE-RESISTING SYSTEM OF |
| | THE BUILDING: |
| | 1.BASIC WIND SPEED (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR). |
| | 2.WIND IMPORTANCE FACTOR, I W , AND |
| | BUILDING CLASSIFICATION FROM TABLE |
| | 1604.5 OR TABLE 6-1, ASCE 7 AND BUILDING |
| | CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | 3.WIND EXPOSURE, IF MORE THAN ONE |
| | WIND EXPOSURE IS UTILIZED, THE WIND |
| | EXPOSURE AND APPLICABLE WIND DIRECTION |
| | SHALL BE INDICATED. |
| | 4.THE APPLICABLE ENCLOSURE |
| | CLASSIFICATIONS AND, IF DESIGNING WITH |
| | ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5.COMPONENTS AND CLADDING. THE |
| | DESIGN WIND PRESSURES IN TERMS OF PSF |
| | (KN/M 2 ) TO BE USED FOR THE DESIGN OF |
| | EXTERIOR COMPONENT AND CLADDING |
| | MATERIALS NOT SPECIFICALLY DESIGNED BY |
| | THE REGISTERED DESIGN PROFESSIONAL. |
| | |
| | 4) THE PERSONS RESPONSIBLE FOR THE WIND |
| | DESIGN SHALL SIGN THE DRAWINGS PER |
| | 106.3.4.3 FBC |
| | |
| | 5) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |