| 2006-09-19 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW, NOT ALL NOTES BELOW |
| | PERTAIN TO THE TECHNICAL ELECTRICAL |
| | REVIEW OR APPLY TO KAMM CONSULTING |
| | ENGINEERS. |
| | |
| | |
| | 1) NOTE: PLEASE SEEE NOTICE OF |
| | COMMENCMENT SUBMITTED HAS EXPIRED. |
| | PLEASE ALSO KNOW, AS THE GENERAL |
| | DESCRIPTION AS ORIGINALLY STATED ALSO |
| | DID NOT INCLUDE THE BRIDGE. |
| | PLEASE SEE FS 713.13(2). |
| | NOC'S EXOIRED AFTER ONE YEAR, EVEN IF |
| | JOB SITE WORK IS ON GOING. |
| | |
| | 2) NOTE: PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004 AND FS |
| | 481.219 FOR MISSING INFORMATION REQUIRED |
| | ON THE TITLE BLOCKS FOR THE ARCHITECT |
| | AND ARCHITECTURAL FIRM. |
| | ** REQUIRED WHETHER COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS FOR STRUCTURAL |
| | ENGINEERING FIRM AS REQUIRED UNDER FAC |
| | 61G15-23.002, AND FS 471.023. |
| | MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER ALSO. |
| | ** REQUIRED WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | ** PLEASE SEE SHEETS ALSO REFERENCE THE |
| | 2001 FBC INTO DESIGN. PLEASE SEE |
| | BUIDLING REVIEW NOTES AS THIS PROJECT |
| | WAS SUBMITTED AFTER OCT 1ST, 2005 WHICH |
| | NOW REQUIRES THE DESIGNS, CODES STATE AS |
| | THE 2004 FBC. |
| | ** NOT AN ELECTRICAL COMMENT, ONLY GIVEN |
| | FOR INFORMATIONAL PURPOSE. |
| | |
| | 4) NOTE: PLEASE PROVIDE A NOTE ON THE |
| | ELECTRICAL E-1 AS EACH ELECTRICAL BOX ON |
| | THE BRIDGE SHALL CONTAIN LABLELING FOR |
| | WHERE THE CIRCUIT IS BEING FED FROM. |
| | |
| | 5) NOTE: PLEASE PROVIDE CURRENT AND |
| | RELEVANT CODES/ EDITIONS ON PLANS. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72 ETC. |
| | |
| | 6) NOTE: PLEASE PROVIDE BONDING OF NEW |
| | STEEL/STRUCTURE TO THE ELECTRICAL SYSTEM |
| | OF THE EXISTING BUILDING WHICH IS |
| | PROVIDING POWER FOR LIGHTING TO NEW |
| | WALKWAY. |
| | 250.50, 250.104 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |