| 2007-02-24 17:46:37 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 EXISTING BUILDING |
| | MUNICIPAL CODE |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES FOR EACH SPACE PER TABLES |
| | 1004.2.1. AND 403.1. |
| | ****RESPONSE NOTED, BUT ALL UNITS WITH A STORAGE |
| | OCCUPANCY REQUIRES A SERVICE SINK. PLEASE INDICATE |
| | LOCATION OF REQUIRED SINK. (SUITES 1,2,3,4 & 5,6 & 9). |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK - PER C. WILLIAMS |
| | |
| | 7. CHANGE OF OCCUPANCY FOR ANY OR ALL |
| | UNITS IS REQUIRED. THIS CAN BE VERIFIED |
| | WITH PREVIOUS OCCUPATIONAL LICENSES. |
| | SECTION 306.1. INDICATE ALL UNITS THAT |
| | HAVE A CHANGE OF OCCUPANCY. INDICATE |
| | PREVIOUS OCCUPANCY, AND WHAT OCCUPANCY |
| | IT WILL BE CHANGED TO. |
| | ****RESPONSE NOTED, BUT UNIT 6 IS INDICATED AS A |
| | STORAGE OCCUPANCY. WAS THIS A CHANGE OF OCCUPANCY? |
| | |
| | 8. A BUILDING, FACILITY, OR ELEMENT THAT |
| | IS ALTERED SHALL COMPLY WITH CHAPTER 11. |
| | SUBMIT DETAILS FOR ALL TOILET ROOMS & |
| | REQUIRED DRINKING FOUNTAINS PER SECTIONS |
| | 11-4.15, 11-4.16, 11-4.19, 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT PLEASE SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | DRINKING FOUNTAINS... |
| | A. INDICATE IF THE DRINKING FOUNTAINS ARE FLOOR MOUNT |
| | OR CANTILEVERED TYPE. IF CANTILEVERED TYPE, THE |
| | CLEARANCE SHALL BE INDICATED PER SECTION 11-4.15.4. |
| | B. 11-4.15.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. |
| | WATER CLOSETS... |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | LAVS... |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC SHOWING |
| | THE CONNECTION TO THE BUILDING DRAIN AND THE VENT |
| | PIPING FOR THE SERVICE SINKS REQUIRED IN TABLE 403.1. |
| | THE SERVICE SINK SHALL DISCHARGE DOWNSTREAM OF THE |
| | BATHROOM FIXTURES PER SECTION 909.1. SECTION |
| | 106.3.5.1.3(4)(6)(13). |
| | |
| | |