| Plan Review Notes For Permit 06082252 |
| Permit Number |
06082252 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-13 09:20:35 | -----------------DENIED------------------ | | | | | | PLANS CONTAIN NO INFORMATION REGARDING SIZE, LOCATION | | | AND NUMBER OF FIRE DAMPERS REQUIRED AS A RESULT OF THE | | | ADDITION OF THE RATED TENANT SEPARATIONS. PLEASE | | | PROVIDE ADDITIONAL INFORMATION, PERHAPS INCLUDING FIRE | | | DAMPER SUBMITTALS/INSTALLATION INSTRUCTIONS. | | | | | | AN ATTEMPT WAS MADE TO CONTACT THE ENGINEER VIA | | | VOICEMAIL. A RETURN CALL WAS NOT RECEIVED. | | | | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|