Plan Review Notes
Plan Review Notes For Permit 06082252
Permit Number 06082252
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-11 16:35:16** UNSAT ** 2ND REVIEW
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS SHALL STATE ALL RELEVANT
 CODES FOR DESIGN. PLEASE SEE PLANS NOTES MENTIONS THE
 2001 FBC.
 PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS
 REVIEWER AND PLEASE SEE ANY OTHER RELEVANT CODES WHICH
 MAY BE REQUIRED BY OTHER REVIEWER(S).
 2002 NFPA-70, 2002 NFPA-72, 2003, NFPA-101, AND THE
 2004 FBC.
 PLEASE SEE SOME LOCATIONS ON PLANS WHICH MENTIONS *PALM
 BEACH COUNTY*.
  
 2) NOTE: PLEASE CLARIFY THE DESIGNERS OF RECORD FOR
 SCOPES AS SHOWN. PLEASE SEE SOME SHEETS WHICH CONTAIN
 ELECTRICAL AND ELECTRICAL INFORMATION IS DONE BY A
 DIFFERENT DESIGN PROFESSIONAL THAN THAT ON ELECTRICAL
 SHEETS. PLEASE SEE OTHER SHEETS WITH NOTES FOR
 ELECTRICAL ALSO CONTAIN YET ANOTHER DESIGNER OF
 RECORD??
 THIS IS UNCLEAR AT THIS TIME.
 FS 471.025
  
 3) NOTE: PLEASE KNOW, ALL SPACES SHALL STATE THE
 OCCUPANCY CLASSIFICATIONS AND/OR THE INTENDED OCCUPANCY
 CLASSIFICATIONS.
 PLEASE SEE THE STORAGE AREAS IF HAZARDOUS NEED TO BE
 STATED AS SUCH.
 PLEASE SEE THAT SPACES 6 AND 7 WHICH ARE BEING SHOWN AS
 SEPARATE TENANTS AND OCCUPANCIES ARE BEING SHOWN WITH
 SEVERAL OPENINGS AND DOORS BETWEEN THE TWO. ACCESS FROM
 ONE TENANT TO ANOTHER OR THROUGH ANOTHER IS UNCLEAR.
 HOW DOES THIS MEET TENANT SEPARATION OF OCCUPANCIES?
 *PLEASE SEE ANY BUILDING REVIEW AND/OR FIRE REVIEW
 COMMENTS FOR THIS.
  
 4) NOTE: PLEASE SEE PERMIT APPLICATION SCOPE OF WORK
 DOES NOT CORRELATE WITH THE PLANS SUBMITTED IN ANY
 FASHION. PLEASE SEE THE SQ FOOTAGE AND THE PLANS
 INDICATE ALMOST TWICE THE SQ FT?? PLEASE CORRELATE.
 PLEASE SEE PERMIT APPLICATION WHICH REQUIRES PROJECT
 AND SCOPE TO BE DESCRIBED IN DETAIL.
  
 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE
 VALUE FOR THE COMPLETE SCOPE OF WORK WAS EXTREMELY LOW
 AND THE VALUE WAS ONLY INCREASED TO $38K WHICH WOULD
 NOT COVER THE ELECTRICAL ALONE FOR MATERIALS OR LABOR.
 PLEASE KNOW THAT WAS VALUE WILL BE ASSESSED FOR ACTUAL
 SCOPE AS APPLIED AND SHOWN ON PLANS.
 *PREVIOUS REVIEW NOTE**
 PLEASE SEE THE VALUE IS EXTREMELY LOW AS STATED FOR
 THE SCOPE OF WORK BEING PROPOSED. PLEASE SEE THAT ONE
 WILL BE ASSESSED PER MARSHALL'S & SWIFT GUIDE AS
 ADOPTED UNDER THE FBC IF AN ACCURATE FIGURE IS NOT
 ADJUSTED FOR SCOPE.
 FBC 108.3, MUST INCLUDE ALL LABOR AND MATERIALS,
 WHETHER OR NOT OWNER SUPPLIED.
  
 6) NOTE: PLEASE SEE FBC CHAPTER 13, PLEASE SUBMIT
 COMPLETED PLANS FOR SYSTEM BEING INSTALLED. PLEASE
 INDICATE AND SHOW ALL OVER RIDES ON PLANS, AT LOCATIONS
 AS REQUIRED UNDER THE FBC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 PLEASE SEE NOTE #1 WHICH MENTIONS TIME FOR DEVICE TO
 TURN OFF IN (30FEET) THIS SEEMS TO BE A MISPRINT.
 PLEASE SEE THERE ARE AREAS WHICH A SINGLE CEILING
 MOUNTED OC SENSOR WILL NOT PROVIDE THE NEEDED COVERAGE
 WHEN AN OCCUPANT ENTERS A SPACE.
 PLEASE CHECK THE LIMITATIONS ON THE DEVICES BEING
 SPECIFIED ON PLANS AND ADJUST ACCORDINGLY. PLEASE SEE
 ANY AREAS WHICH WALLS WOULD BLOCK THESE DEVICES WOULD
 BE REQUIRED TO CONTAIN ANOTHER DEVICE FOR COVERAGE FOR
 LIFE SAFETY. (LS101 7.8)
 PLEASE SEE SUBMITTED PACKAGE DID NOT SEEM TO CONTAIN
 ANY ENERGY CALCULATIONS?
 13-415.1.AB.1.(THE LPD?S SEEM TO BE OK.)
 PLEASE ALSO SUBMIT ENERGY CALCULATIONS SIGNED, DATED
 AND SEALED.
 13-415.1.AB.1.
 PLEASE SEE 13-415.ABC.1.4 FOR EXT LTS.
  
 7) NOTE: PLEASE CLARIFY HOW THE LOADS FOR SHOW WINDOW
 AREAS WERE DERIVED. PLEASE SEE 220.12.
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, IF ANY SPACE WILL BE MERCANTILE, AND HAVE
 WINDOWS IN FRONT FACING STREET WHICH IS SUBJECT TO
 PEDESTRIAN TRAFFIC, RECEPTS ABOVE THOSE WINDOWS WILL BE
 REQUIRED.
 210.62
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS, WHICH IS ONLY BEING NOTED AT THIS
 TIME.
  
 9) NOTE: PLEASE SEE BASED ON PREVIOUS BUILDING REVIEW
 COMMENTS, THERE MAY STILL BE ADUSTMENTS IN PLANS WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]