| 2007-02-11 16:35:16 | ** UNSAT ** 2ND REVIEW |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THAT PLANS SHALL STATE ALL RELEVANT |
| | CODES FOR DESIGN. PLEASE SEE PLANS NOTES MENTIONS THE |
| | 2001 FBC. |
| | PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS |
| | REVIEWER AND PLEASE SEE ANY OTHER RELEVANT CODES WHICH |
| | MAY BE REQUIRED BY OTHER REVIEWER(S). |
| | 2002 NFPA-70, 2002 NFPA-72, 2003, NFPA-101, AND THE |
| | 2004 FBC. |
| | PLEASE SEE SOME LOCATIONS ON PLANS WHICH MENTIONS *PALM |
| | BEACH COUNTY*. |
| | |
| | 2) NOTE: PLEASE CLARIFY THE DESIGNERS OF RECORD FOR |
| | SCOPES AS SHOWN. PLEASE SEE SOME SHEETS WHICH CONTAIN |
| | ELECTRICAL AND ELECTRICAL INFORMATION IS DONE BY A |
| | DIFFERENT DESIGN PROFESSIONAL THAN THAT ON ELECTRICAL |
| | SHEETS. PLEASE SEE OTHER SHEETS WITH NOTES FOR |
| | ELECTRICAL ALSO CONTAIN YET ANOTHER DESIGNER OF |
| | RECORD?? |
| | THIS IS UNCLEAR AT THIS TIME. |
| | FS 471.025 |
| | |
| | 3) NOTE: PLEASE KNOW, ALL SPACES SHALL STATE THE |
| | OCCUPANCY CLASSIFICATIONS AND/OR THE INTENDED OCCUPANCY |
| | CLASSIFICATIONS. |
| | PLEASE SEE THE STORAGE AREAS IF HAZARDOUS NEED TO BE |
| | STATED AS SUCH. |
| | PLEASE SEE THAT SPACES 6 AND 7 WHICH ARE BEING SHOWN AS |
| | SEPARATE TENANTS AND OCCUPANCIES ARE BEING SHOWN WITH |
| | SEVERAL OPENINGS AND DOORS BETWEEN THE TWO. ACCESS FROM |
| | ONE TENANT TO ANOTHER OR THROUGH ANOTHER IS UNCLEAR. |
| | HOW DOES THIS MEET TENANT SEPARATION OF OCCUPANCIES? |
| | *PLEASE SEE ANY BUILDING REVIEW AND/OR FIRE REVIEW |
| | COMMENTS FOR THIS. |
| | |
| | 4) NOTE: PLEASE SEE PERMIT APPLICATION SCOPE OF WORK |
| | DOES NOT CORRELATE WITH THE PLANS SUBMITTED IN ANY |
| | FASHION. PLEASE SEE THE SQ FOOTAGE AND THE PLANS |
| | INDICATE ALMOST TWICE THE SQ FT?? PLEASE CORRELATE. |
| | PLEASE SEE PERMIT APPLICATION WHICH REQUIRES PROJECT |
| | AND SCOPE TO BE DESCRIBED IN DETAIL. |
| | |
| | 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE |
| | VALUE FOR THE COMPLETE SCOPE OF WORK WAS EXTREMELY LOW |
| | AND THE VALUE WAS ONLY INCREASED TO $38K WHICH WOULD |
| | NOT COVER THE ELECTRICAL ALONE FOR MATERIALS OR LABOR. |
| | PLEASE KNOW THAT WAS VALUE WILL BE ASSESSED FOR ACTUAL |
| | SCOPE AS APPLIED AND SHOWN ON PLANS. |
| | *PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THE VALUE IS EXTREMELY LOW AS STATED FOR |
| | THE SCOPE OF WORK BEING PROPOSED. PLEASE SEE THAT ONE |
| | WILL BE ASSESSED PER MARSHALL'S & SWIFT GUIDE AS |
| | ADOPTED UNDER THE FBC IF AN ACCURATE FIGURE IS NOT |
| | ADJUSTED FOR SCOPE. |
| | FBC 108.3, MUST INCLUDE ALL LABOR AND MATERIALS, |
| | WHETHER OR NOT OWNER SUPPLIED. |
| | |
| | 6) NOTE: PLEASE SEE FBC CHAPTER 13, PLEASE SUBMIT |
| | COMPLETED PLANS FOR SYSTEM BEING INSTALLED. PLEASE |
| | INDICATE AND SHOW ALL OVER RIDES ON PLANS, AT LOCATIONS |
| | AS REQUIRED UNDER THE FBC. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 |
| | PLEASE SEE NOTE #1 WHICH MENTIONS TIME FOR DEVICE TO |
| | TURN OFF IN (30FEET) THIS SEEMS TO BE A MISPRINT. |
| | PLEASE SEE THERE ARE AREAS WHICH A SINGLE CEILING |
| | MOUNTED OC SENSOR WILL NOT PROVIDE THE NEEDED COVERAGE |
| | WHEN AN OCCUPANT ENTERS A SPACE. |
| | PLEASE CHECK THE LIMITATIONS ON THE DEVICES BEING |
| | SPECIFIED ON PLANS AND ADJUST ACCORDINGLY. PLEASE SEE |
| | ANY AREAS WHICH WALLS WOULD BLOCK THESE DEVICES WOULD |
| | BE REQUIRED TO CONTAIN ANOTHER DEVICE FOR COVERAGE FOR |
| | LIFE SAFETY. (LS101 7.8) |
| | PLEASE SEE SUBMITTED PACKAGE DID NOT SEEM TO CONTAIN |
| | ANY ENERGY CALCULATIONS? |
| | 13-415.1.AB.1.(THE LPD?S SEEM TO BE OK.) |
| | PLEASE ALSO SUBMIT ENERGY CALCULATIONS SIGNED, DATED |
| | AND SEALED. |
| | 13-415.1.AB.1. |
| | PLEASE SEE 13-415.ABC.1.4 FOR EXT LTS. |
| | |
| | 7) NOTE: PLEASE CLARIFY HOW THE LOADS FOR SHOW WINDOW |
| | AREAS WERE DERIVED. PLEASE SEE 220.12. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, IF ANY SPACE WILL BE MERCANTILE, AND HAVE |
| | WINDOWS IN FRONT FACING STREET WHICH IS SUBJECT TO |
| | PEDESTRIAN TRAFFIC, RECEPTS ABOVE THOSE WINDOWS WILL BE |
| | REQUIRED. |
| | 210.62 |
| | |
| | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS, WHICH IS ONLY BEING NOTED AT THIS |
| | TIME. |
| | |
| | 9) NOTE: PLEASE SEE BASED ON PREVIOUS BUILDING REVIEW |
| | COMMENTS, THERE MAY STILL BE ADUSTMENTS IN PLANS WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |