2006-10-05 00:00:00*****DENIED*****
  
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OF
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL, DUST AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 4.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.
  
 5.) INTERIOR WALL AND CEILING FINISH
 SHALL BE CLASS "A" OR CLASS "B" IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION,
 SECTION 10.2.
  
 6.) HOW WILL THE SCOPE OF WORK AFFECT
 THE ARRANGEMENT/LOCATION OF EXIT SIGNS,
 EMERGENCY LIGHTS, FIRE EXTINGUISHERS,;
 AND IF EQUIPPED, SPRINKLER OR FIRE ALARM
 SYSTEMS?
  
 7.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF A FIRE PROTECTION
 SYSTEM, PROVIDESEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS.
  
  
  