| 2006-09-17 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW, IT IS KNOWN TO THIS |
| | OFFICE SOME OF THIS WORK WAS ALREADY |
| | DONE FOR THESE SEPARATION WALLS ETC. |
| | |
| | 1) NOTE: PLEASE SEE FAC 61G15-23.002 |
| | WHICH REQUIRES TITLE BLOCKS ON ALL |
| | SHEETS. |
| | PLEASE SEE PLANS ARE BEING DONE BY A |
| | STRUCTURAL ENGINEER KNOWN TO THIS |
| | OFFICE. PLEASE SEE FS 471.025. |
| | |
| | 2) NOTE: PLEASE SEE THAT PLANS STATE ALL |
| | RELELVANT CODES FOR DESIGN. PLEASE SEE |
| | PLANS NOTES MENTIONS THE 2001 FBC. |
| | PLEASE STAE THE FOLLOWING AT A MINIMUM |
| | FOR THIS REVIEWER AND PLEASE SEE ANY |
| | OTHER RELEVANT CODES WHICH MAY BE |
| | REQUIRED BY OTHER REVIEWER(S). |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101, AND THE 2004 FBC. |
| | |
| | 3) NOTE: PLEASE PROVIDE AND SUBMIT |
| | COMPLETE LOAD CALCULATIONS FOR THE |
| | ENTIRE SERVICE. PLEASE SEE THE FOLLOWING |
| | NOTE ALSO FOR SERVICES AS SHOWN ON |
| | RISER. |
| | 220,215.5 ETC. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE SERVICES AS SHOWN |
| | ARE NOTE PERMITTED AT THIS TIME. PLEASE |
| | SEE 230.2. PLEASE ALSO SEE MORE THAN |
| | 6-MEANS OF DISCONNET FOR BUILDING. |
| | PLEASE SEE FBC DEFINITIONS, THIS IS ONE |
| | BUILDING AND AT THIS TIME ONLY ONE |
| | SERVICE WILL BE GRANTED. |
| | |
| | 5) NOTE: PLEASE PROVIDE COMPLETE FAULT |
| | CURRENT CALCULATIONS FOR SERVICE AND THE |
| | AVAILABLE FUALT CURRENT AT MAIN(S). |
| | IT IS NOTED BY THIS OFFICE THAT THE 10K |
| | RATING IS SHOWN, HOWEVER COMPLETE CALCS |
| | ARE BEING REQUESTED BY THIS AHJ. |
| | |
| | 6) NOTE: PLEASE KNOW, ALL SPACES SHALL |
| | STATE THE OCCUPANCY CLASSIFICATIONS |
| | AND/OR THE INTENED OCCUPANCY |
| | CLASSIFICATIONS. |
| | PLEASE KNOW, IT HAS COME TO OUR |
| | ATTENTION THAT SOME SPACE WERE BEING |
| | USED AS AN ASSEMBLY OCCUPANCY ETC. |
| | PLEASE SEE INDICATE ALL ELECTRICAL |
| | REQUIREMENTS FOR THE "AUTOMOTIVE REPAIR |
| | SHOP" AS KNOWN TO THIS OFFICE AND |
| | INDIACTE D ON PLANS. |
| | PLEASE SEE NEC 511 AS THIS IS ONEOF THE |
| | HAZARDOUS LOCATIONS. |
| | PLEASE SHOW INDICATE THE DOOR OPENINGS |
| | FOR THIS AUTOMOTICE REPAIR LOCATION ON |
| | PLANS. |
| | ** PLEASE SEE FIRE AND BUIDLING REVIEW |
| | COMMENTS FOR THIS. |
| | |
| | 7) NOTE: PLEASE SEE PERMIT APPLICATION |
| | STATES ONE SQ FOOTAGE AND THE PLANS |
| | INDICATE ALMOST TWICE THE SQ FT?? PLEASE CORRELATE. |
| | |
| | 8) NOTE: PLEASE SEE THE VALUE IS |
| | EXTREMEMLY LOW AS STATED FOR THE SCOPE |
| | OF WORK BEING PROPOSED. PLEASE SEE THAT |
| | ONE WILL BE ASSESSED PER MARSHALL'S & |
| | SWIFT GUIDE AS ADOPTED UNDER THE FBC IF |
| | AN ACCURATE FIGNURE IS NOT ADJUSTED FOR |
| | SCOPE. |
| | FBC 108.3, MUST INCLUDE ALL LABOUR AND |
| | MATERIALS, WHETHER OR NOT OWNER |
| | SUPPLIED. |
| | |
| | 9) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | PLEASE SUBMIT COMPLETED PLANS FOR SYSTEM |
| | BEING INSTALLED. PLEASE INDICATE AND |
| | SHOW ALL OVER RIDES ON PLANS, AT |
| | LOCATIONS AS REQUIRED UNDER THE FBC. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 |
| | PLEASE PROVIDE COMPLETE LIGHTING DENSITY |
| | LOADS AS REQUIRED PER 13-415.2.ABC.1, |
| | TABLES 415.2.C.1, 415.2.B.1. |
| | PLEASE ALSO SUBMIT ENERGY CALCULATIONS |
| | SIGNED, DATED AND SEALED. |
| | 13-415..1.AB.1. |
| | PLEASE SEE 13-415.ABC.1.4 FOR EXT LTS. |
| | |
| | 10) NOTE: PLEASE KNOW, IF ANY SPACE WILL |
| | BE MERCHANTILE, AND HAVE WINDOWS IN |
| | FRONT FACING STREET WHICH IS SUBJECT TO |
| | PEDESTRIAN TRAFFIC, RECETPS ABOVE THSOE |
| | WINDOWS WILL BE REQUIRED. |
| | 210.62 |
| | |
| | 11) NOTE: PLEASE SEE FORE REVIEW |
| | COMMENTS AS THE LARGER BATHRM WILL ALSO |
| | REQUIRE AN EM BATTERY BACK UP FIXTURE OF |
| | SOME SORT. |
| | LS 101 7.8,7.9. |
| | |
| | ** PLEASE KNOW AT THIS TIME DUE TO SOME |
| | CHANGES WHICH WILL BE REQUIRED IN |
| | SERVICE ETC, PLANS AS SUBMITTED MAY HAVE |
| | FUTURE COMMENTS UPON NEXT REVIEW. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-09-12 00:00:00 | REVIEW ON HOLD. |
| | PLANS WILL BE GOING INTO "F" STATUS ONCE |
| | REVIEW IS COMPLETE. |