| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE 3/0 SERVICE CONDUCTORS ARE NOT |
| | LARGE ENOUGH FOR THE CALCULATED LOAD. |
| | SEE 310.15(B)(6). |
| | |
| | 2} THERE IS NO WATER HEATER LISTED IN |
| | THE HOUSE PANEL, YET THE REQUIRED |
| | LAUNDRY CIRCUIT (WASHER) IS LISTED IN |
| | THAT PANEL. PLEASE VERIFY THERE IS NO |
| | HOT WATER TO BE SUPPLIED TO THE WASHER. |
| | THE GARAGE PLUMBING DOES NOT SEEM TO BE |
| | ON THE PLUMBING RISR. |
| | |
| | 3} THE BREAKFAST ROOM LISTED ON THE |
| | PANEL SCHEDULES,PANELS 1, 2, AND 3 MUST |
| | BE ON A 20AMP CIRCUIT PER 210.52(B)(1). |
| | |
| | 4} THE BATH CIRCUITS SHALL BE 20 AMP. |
| | 210.11(C)(3). |
| | |
| | 5} PLEASE SEE ALL KITCHEN RECEPTACLES |
| | MUST COMPLY WITH 210.52(B). TWO |
| | RECEPTACLES IN UNIT #1, ONE LISTED ON |
| | C13 AND THE OTHER NOT LISTED BUT ON WITH |
| | A LIVING ROOM OUTLET, DO NOT COMPLY. |
| | |
| | 6} THE BREAKFAST ROOM CIRCUIT IN UNIT #2 |
| | MAY NOT FEED THE LIVING ROOM OUTLETS. |
| | 210.52(B)(2). |
| | |
| | 7} UNIT #3 KITCHEN NEEDS A RECEPTACLE |
| | ADDED BY THE RANGE TO COMPLY WITH |
| | 210.52(C)(1). |
| | |
| | 8} THE SMOKE DETECTOR LOCATION OUTSIDE |
| | THE BEDROOMS DO NOT COMPLY WITH THE |
| | "IMMEDIATE VICINITY" INTENT OF R313.1.1 |
| | 2. |
| | |
| | |