Plan Review Notes
Plan Review Notes For Permit 06082225
Permit Number 06082225
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-10 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS SHALL INDICATE
 ALL RELEVANT CODES TO PROPOSED PROJECT
 AND DESIGN.
 PLEASE SEE THE FOLLOWING ARE REQUIRED AT
 A MINIMUM.
 2002 NFPA-70, 2002 NFPA-110, 2004 FBC.
  
 2) NOTE: PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL INCLUDE ALL
 LABOUR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SPPLIED.
 FBC 108.3.
 ** VALUE AS SHOWN ON APPLICATION IS LOW,
 PLEASE SEE THAT IF NOT ADJUSTED, A VALUE
 WILL BE ASSESSED USING THE MARSHALL'S &
 SWIFT GUIIDE AS ADOPTED BY THE FBC.
 PLEASE ALSO KNOW, SIGNED, CONTRACTS FOR
 ALL EQUIPMENT, ALL LABOUR AND MATERIALS
 MAY ALSO BE REQUESTED.
 THE VALUE ON THE GEN ALONE IS ABOVE THE
 VALUE APPLIED FOR.
  
 3) NOTE: PLEASE SEE THE PROPOSED SCOPE
 AND GROUPING OF DISCONNECTS IS NOT CODE
 COMPLIANT. PLEASE ALSO SEE RISER IS NOT
 COMPLETE AT THIS TIME AS THE FEEDERS
 FROM THE LOAD SIDE OF THE ATS DO NOT
 APPEAR TO GO ANYWHERE?
 PLEASE SEE 225.34 AND 230.72 FOR
 GROUPING OF MAINS. THE NEW PROPOSED MAIN
 2 OF 2 IS OUTSIDE AND THE OTHER MAIN 1
 IS INSIDE. THE REQUIRED MAINS AND
 DISCONNECTS ARE NOT GROUPED AS REQUIRED.
 PLEASE SEE THE PERMIT APPLIED FOR #
 06081714 HAS BEEN PLACED INTO A "HOLD"
 STATUS UNTIL DESIGN IS ADJUSTED.
 PLEASE PROVIDE A COMPLETE LAYOUT OF ALL
 THE EXISTING SERVICE AND NEW WORK.
 PLEASE KNOW THE ATS AND DISCONNECT BEING
 SHOWN AS EXISTING ON THIS RISER SHALL BE
 SHOWN AS NEW AS THIS SEPARATE PERMIT AS
 SHOWN WILL NOT BE GRANTED.
 215.5,225.31-225.39, 230.72ETC
  
 4) NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONS FOR PROPOSED GENERATOR AND
 ALL LOADS INTENDED FOR USE. PLEASE KNOW
 IF LOAD SHEDDING IS BEING PROPOSED, MUST
 SHOW LOAD SHEDDING DETAILS.
 ** PLEASE SEE 702.5, THE NOTE WHICH IS
 PLACE ON PLANS MENTIONS THE CONSUMER CAN
 MANUALLY TURN OFF BREAKERS TO CHOSE
 LOAD. PLEASE SEE 700.5 AND 701.5 THE AHJ
 AND OTHER CODES DETERMINE WHAT IS
 REQUIRED ON EMERGENCY AND LEGALLY
 REQUIRED STAND-BY SYSTEMS WHERE 702.5
 MENTIONS THE CONSUMER CAN CHOSE WHICH
 LOADS THEY WANT TO HAVE ON AN OPTIONAL
 STAND-BY SYSTEM. THE PROPOSED BACK UP
 SYSTEM ON AN "AUTOMATIC STAND-BY" STILL
 MUST BE SIZED PER THE LOADS INTENDED.
 THE CODE DOES NOT STATE THE "OWNER CAN
 TURN OFF BREAKERS TO CHOOSE LOADS"
 THE SYSTEN AS SHOWN IS NOT BEING SHOWN A
 "MANUAL TRANSFER".
 220.3,220.10,220.11,220.13, ETC.
 PLEASE SEE 215.3,230.42 FORANY
 CONTINUOUS LOADS.
  
 5) NOTE: PLEASE SEE PERMIT APPLICATION
 SHALL STATE THE TENANT SPACE/UNIT
 NUMBER. PLEASE SEE THAT THE PERMIT
 APPLICATION SHALL ALSO STATE THE PROJECT
 IN DETAIL. PLEASE SEE APPL ONLY MENTIONS
 "INSTALL GENERATOR PAD", A HAND WRITTEN
 NOTE INCLUDING THE GENERATOR WAS DONE
 THE FRONT COUNTER STAFF.
 PLEASE LIST THE SIZE OF UNIT, ATS ,
 SUB-BASE FUEL ETC.
  
 6) NOTE: PLEASE PROVIDE A LEGAL SURVEY
 SHOWING THE EXACT LOCATION OF THE
 GENERATOR LOCATED ON PROPERTY INCLUDING
 ALL SETBACKS ETC. THIS WILL ALSO BE IN
 THE ZONING REVIEW NOTES.
 PLEASE KNOW, CODE COMPLIANCE CAN NOT BE
 DETERMINED AT THIS TIME.
  
 7) NOTE: PLEASE SEE THAT ONCE THE
 UNIT/SUITE # IS OBTAINED, PLEASE INCLUDE
 ON TITLE BLOCKS WITH THE ADDRESS AS
 SHOWN.
 FAC 61G15-23.002
  
 8) NOTE: PLEASE SEE RISER CONTAINS THE
 SYMBOL FOR THE KEYNOTE #1 JUST BELOW
 TENANTS MCB #1 AND #2, HOWEVER KEY NOT
 #1 DOES NOT SEEM TO CORRELATE.
  
 ** ONE COPY OF THE ELECTRICAL RISER IN
 ONE SET HAS BEEN RETAINED BY THIS
 OFFICE.
  
 ** PLEASE KNOW AS THERE AREITEMS FOR
 CODE COMPLIANCE NOT YET SUBMITTED AND
 DESIGN AS SHOWN WILL BE CHANGING, THERE
 MAY BE COMMENTS ON NEW PLANS SUBMITTED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]