Plan Review Notes
Plan Review Notes For Permit 06082225
Permit Number 06082225
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-13 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ONE OF THE THREE SETS OF PLANS IS
 MISSING PAGE 3 OF 4 (E5.1).
  
 3) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE SPECIFY THE SIZE OF THE SPECIFIC
 GENERATOR(WXL) THAT WILL BE INSTALLED
 AND SPECIFY THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
  
 4) SPECIFY THE BASIC WIND SPEED ON THE
 PLAN. SEE FBC 1603.1.4 AND 1609.1.3.
  
 5) SPECIFY THE UNIT/SUITE THAT THE
 GENERATOR WILL SERVICE ON THE PERMIT
 APPLICATION.
  
 6) THE PROJECT IS LOCATED IN AN "AO"
 FLOOD ZONE. EQUIPMENT MUST BE LOCATED 6"
 ABOVE BASE FLOOD ELEVATION. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  