| Plan Review Notes For Permit 06082225 |
| Permit Number |
06082225 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-09-13 00:00:00 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) ONE OF THE THREE SETS OF PLANS IS | | | MISSING PAGE 3 OF 4 (E5.1). | | | | | | 3) GENERATOR SLAB & ANCHOR REQUIREMENT | | | PLEASE SPECIFY THE SIZE OF THE SPECIFIC | | | GENERATOR(WXL) THAT WILL BE INSTALLED | | | AND SPECIFY THE MINIMUM EDGE DISTANCE | | | THE DEVICE REQUIRES WITHOUT LOAD | | | REDUCTION. | | | | | | 4) SPECIFY THE BASIC WIND SPEED ON THE | | | PLAN. SEE FBC 1603.1.4 AND 1609.1.3. | | | | | | 5) SPECIFY THE UNIT/SUITE THAT THE | | | GENERATOR WILL SERVICE ON THE PERMIT | | | APPLICATION. | | | | | | 6) THE PROJECT IS LOCATED IN AN "AO" | | | FLOOD ZONE. EQUIPMENT MUST BE LOCATED 6" | | | ABOVE BASE FLOOD ELEVATION. AN ELEVATION | | | CERTIFICATE WILL BE REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | | | | |
|