| Plan Review Notes For Permit 06082221 |
| Permit Number |
06082221 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-08 08:40:37 | DENIED; | | | 1.A DRINKING FOUNTAIN IS REQUIRED NOT A WATER COOLER. A | | | DRAIN IS REQUIRED, PLEASE SHOW ON SANITARY RISER | | | DIAGRAM. SEE SECTION 410.1 | | | 2. DRINKING FOUNTAIN TO MEET ACCESSIBILITY CODES | | | SECTION 11-4.1.3(10)A HI-LOW FOUNTAIN OR ONE D/F SET | | | AT HANDICAP HIGHT WITH A CUP DISPENSOR. SHOW A DETAIL | | | OF DRINKING FOUNTAIN WITH ALL MEASURMENTS REQUIRED BY | | | SECTIONS 11-4.15.1 THRU 11-4.15.5. | | | PLUMBING PLAN REVIEW; | | | JOHN LEECH | | | 805-6695 |
|