| 2006-11-17 10:59:54 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE MOSTLY NEW COMMENTS BASED ON |
| | THE REVISED RISER DIAGRAM SUBMITTED. |
| | |
| | |
| | 1NOTE: PLEASE SEE RISER NOW INDICATES THE NEW "TENANT |
| | SPACE" SERVICE BEING FROM THE BUILDINGS MAIN ELECTRICAL |
| | SERVICE, HOWEVER PLEASE PROVIDE THE SIZE OF THE |
| | EXISTING MAIN ELECTRICAL SERVICE AND THE LOAD ON SUCH |
| | SERVICE WITH THE NEW TENANTS SERVICE LOAD BEING ADDED |
| | TO IT. |
| | NEC 220 |
| | FBC106.3.5.1.2 ADMIN SECT. |
| | |
| | 2) NOTE: PLEASE SUBMIT AND PROVIDE AIC RATINGS FOR NEW |
| | SERVICE EQUIPMENT. PLEASE SEE 110.9 AND 240.12 FOR |
| | SELECTIVE COORDINATION. |
| | |
| | 3) NOTE: PLEASE SEE FIRE PUMP ROOM FOR EXISTING FIRE |
| | PUMP IS BEING SHOWN IN A NEW PROPOSED TENANT SPACE. |
| | PLEASE KNOW, AS THIS BUILDING DOES NOT SEEM TO MEET THE |
| | EXCEPTIONS IN THE CODE UNDER NFPA-20 (FIRE |
| | PUMPS)(CHAPTERS 6-3, AND ALSO CHAPER 7) AND NEC 695, |
| | 230.70, 230.2, , PLEASE KNOW THE ACCESS TO THE FIRE |
| | PUMP AND ANY FIRE PUMP CONTROLLER MUST BE FROM A COMMON |
| | AREA/CORRIDOR OR OUTSIDE. ACCESS THROUGH ONES TENANTS |
| | SPACE IS NOT PERMITTED. |
| | |
| | |
| | 4) NOTE: PLEASE SEE METHOD "A" IS BEING SUBMITTED FOR |
| | THIS NEW SPACE HOWEVER THE METHOD "A" DOES NOT SEEM TO |
| | CORRELATE WITH SCOPE OF. PLEASE SEE OTHER METHODS. "B". |
| | 13-415.2 |
| | PLEASE ALSO SEE THAT THE CALCULATIONS AS SUBMITTED |
| | INDICATE MANUAL CONTROLS, HOWEVER AUTOMATED CONTROLS |
| | ARE SHOWN ON PLANS? |
| | PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ARE |
| | REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER |
| | OF RECORD. |
| | 13-415.1.AB.1, 13-415.2.ABC.1 |
| | |
| | 5) NOTE: PLEASE SE RISER AS SHOWN DOES NOT SEEM TO |
| | INDICATE ANY "MAIN" ON THE LINE SIDE OF THE GUTTER, |
| | THEREFORE AND EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT |
| | BE INSTALLED TO THE METER FROM THE GUTTER. IF A MAIN |
| | DOES EXISTS ON THE LINE SIDE OF THE GUTTER THEN ONE |
| | WOULD BE INSTALLED HOWEVER THE NEW TENANT METER WOULD |
| | THEN CONTAIN NOTES FOR A FLOATING NEUTRAL KIT. |
| | PLEASE SEE 250.6, 250.24B. |
| | |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |