| Date |
Text |
| 2006-09-09 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE 700.12E AS THE |
| | EMERGENCY LTS AND EXT LTS ARE REQUIRED |
| | TO BE CIRCUITED TO THE LOCAL AREA |
| | LIGHTING. |
| | PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE CLARIFY "FIRE PUMP " |
| | EQUIPMENT BEING NOTED AND SHOWN IN ROOM. |
| | THIS ROOM WOULD REQUIRE AT LEAST A 1 HR |
| | RATING IF FULLY SPRINKLED. |
| | PLEASE SEE NFPA-20 FOR INSTALLATION OF |
| | FIRE PUMPS AND REQUIRD SEPARATION. |
| | PLEASE ALSO SEE NEC 695 |
| | |
| | 3) NOTE: PLEASE SEE RISER IS SHOWING A |
| | NEW 150A DISCONNECT BEING PROPOSED ON |
| | THE LINE SIDE THE FPL'S METER SHOWN AS |
| | EXISTING ON RISER?? |
| | PLEASE SEE THE DISCONNECT WOULD BE ON |
| | THE LOAD SIDE OF ANY METERING DEVICES BY |
| | FPL. PLEASE SEE RISER ALREADY SHOWS AN |
| | EXISTING MAIN DISCONNECT?? |
| | PLEASE CLARIFY AND PLEASE SEE FPL |
| | PERMITTED METERING LOCATIONS AND SERVICE |
| | STANDARDS GUIDE. |
| | PLEASE KNOW, AS THIS IS BEING SHOWN AS |
| | EXISTING, PLEASE KNOW A NEW SERVICE FOR |
| | THIS SPACE IS NOT PERMITTED FROM FPL. |
| | THIS SPACE IS NOT A SEPARATE BUILDING |
| | AND ANY NEW "TENANT SPACE" MUST BE FED |
| | FROM THE EXISTING SERVICE FOR THE ENTIRE |
| | BUIDLING. |
| | PLEASE SEE 230.2, 230.70, 230.72. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS (3 OR MORE HRS) AT 125%. |
| | 215.3,230.42 ETC.. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |