| Date |
Text |
| 2006-09-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06082221 |
| | ADD: 500 PALM ST SUITE "C" |
| | CONT: MIKE MOORE CONST |
| | TEL: (561)748-7000 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) SHEET A2.1 THE RESTROOM DOOR IS |
| | MISSING THE 18" CLEAR SPACE LATCH SIDE |
| | OF DOOR.11-4.13.6 MANEUVERING |
| | CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| | DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| | SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| | AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 4) EXISTING BUILDING CODE LEVEL 2 |
| | ALTERATION: 611.1 MINIMUM REQUIREMENTS: ALTERATIONS |
| | SUBJECT TO THIS CHAPTER |
| | SHALL COMPLY WITH THE REQUIREMENTS OF |
| | CHAPTER 13 OF THE FLORIDA BUILDING CODE |
| | BUILDING. |
| | 13-101.1.3 RENOVATIONS. |
| | RENOVATED COMMERCIAL BUILDINGS SHALL, |
| | WHEN APPLICABLE (SEE SECTION 202 ), |
| | COMPLY WITH THE PRESCRIPTIVE |
| | REQUIREMENTS CONTAINED IN FORM 400 C OR |
| | WITH METHOD B OF SUBCHAPTER 13-4 FOR |
| | INSULATION, HVAC SYSTEMS, LIGHTING, |
| | WATER HEATING SYSTEMS AND EXTERIOR |
| | ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED. |
| | |
| | 5)ENGINEER GLENN GOLDBERG SEAL USING THE |
| | PHRASE "CERTIFICATE" |
| | RULE 61G155-23.001(1) F.A.C. |
| | THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS HAS CLEANED UP THE APPEARANCE |
| | OF THE SEAL BY ELIMINATING OBSOLETE |
| | CONTENT AND CHANGING THE WORD |
| | "CERTIFICATE" TO "LICENSE". A GRACE |
| | PERIOD RAN THROUGH DEC. 31,2005. |
| | |
| | 6) ENGINEER GLENN GOLDBERG: |
| | 61G15-23.002(2)FL. ADMIN. CODE. PLANS |
| | SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCLUDE EITHER THE NAME, |
| | ADDRESS AND LICENSE NUMBER OF THE |
| | ENGINEER OR, THE NAME AND LICENSE NUMBER |
| | OF THE ENGINEER AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH |
| | WHICH THE ENGINEER IS PRACTICING |
| | (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 7) VINTAGE DESIGN AND CONSTRUCTION |
| | STRUCTURAL ENGINEER CONSULTANT: |
| | 471.023 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 8) FL BLD CODE 1609.1.4 : COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRUSS ANCHORS, ANCHOR TIES |
| | B) ROOFING ASSEMBLIES |
| | |
| | 9) W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) SHEET S-1 INDICATES THE USE OF AN |
| | EXISTING ROOF DRAIN, IT APPEARS TO |
| | PENETRATE THE EXTERIOR WALL AND DRAIN |
| | INTO AN SCUPPER AND DOWN SPOUT SYSTEM. |
| | NO MENTION OF AN EMERGENCY OVERFLOW? |
| | 1503.4.3 |
| | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW |
| | WATER IS NOT PROVIDED, OVERFLOW SCUPPERS |
| | SHALL BE PLACED IN WALLS OR PARAPETS NOT |
| | LESS THAN 2 INCHES (51 MM) NOR MORE THAN |
| | 4 INCHES (102 MM) ABOVE THE FINISHED |
| | ROOF COVERING AND SHALL BE LOCATED AS |
| | CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| | LEADERS OR DOWNSPOUTS OR WALL AND |
| | PARAPET SCUPPERS. AN OVERFLOW SCUPPER |
| | SHALL BE SIZED IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |