| Date |
Text |
| 2008-05-06 10:38:12 | ** DENIED REVISIONS ** |
| | |
| | 1) NOTE: PLEASE SEE THE VERSION OF THE ENERGY |
| | CALCULATIONS SHALL BE UNDER THE VERSION WHICH PERMIT |
| | APPLICATION WAS MADE. PLEASE KNOW THE VERSION SUBMITTED |
| | AS 2.5 WAS NOT ADOPTED UNTIL 12/8/06. PERMIT WAS |
| | APPLIED FOR BEFORE THIS DATE. VERSION 2.11 WAS IN |
| | AFFECT AT THE APPLICATION DATE. |
| | 13-400.3.A (2005 REVISIONS TO THE 2004 FBC) |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS DO NOT CORRELATE WITH THE |
| | CALCULATIONS OR INPUT DATA REPORT. PLEASE SEE THE |
| | FIXTURES ON PHOTO-METRICS DO NOT COORDINATE WITH THE |
| | LIGHTING FIXTURES ON THE FIXTURE LEGEND. |
| | PLEASE SEE |
| | FOR EXAMPLE: |
| | PLEASE SEE THE FIXTURES SL2 WHICH ARE ON FIXTURE LEGEND |
| | ON E0-00-001 WHICH ARE NOT THE SAME AS SHEET |
| | E1-01-301. |
| | THESE SAME FIXTURES COULD NOT BE LOCATED FOR THE TOTAL, |
| | WATTAGE ETC IN THE IDR. THE IDR CONTAINS FIXTURES FOR |
| | EXTERIOR BUT NOT ALL. |
| | PLEASE SEE THE IDR ALSO CONTAINS A *NON-A/C* ZONE |
| | HOWEVER THESE SL2 FIXTURES ARE NOT IN THIS ZONE. |
| | THE GARAGE ALONE SHOWS A MINIMUM OF 8-SL2 FIXTURES. |
| | THERE ARE NO SL2 FIXTURES ON IDR. SL2 FIXTURES INDICATE |
| | 4-42W COMPACT BULBS. PLEASE GOT THROUGH ALL AND |
| | COORDINATE. |
| | THESE WERE SPECIFICALLY NOTED ON THE PREVIOUS REVIEW |
| | HOWEVER THE SAME FIXTURES ARE THE SAME COMMENTS. ONE |
| | COPY OF THE CALCULATIONS WILL BE RETAINED BY THIS |
| | OFFICE. |
| | **** IT IS IMPORTANT TO KNOW THIS IS NOT AN EXHAUSTED |
| | LIST AS THERE ARE OTHER FIXTURES WHICH DO NOT |
| | COORDINATE. THE EXAMPLES ARE GIVEN AS A BENEFIT ONLY. |
| | |
| | PLEASE SUBMIT COMPLETED REVISED LIGHTING PLANS FOR ALL |
| | REVISED LIGHTING. THIS WOULD INCLUDE ALL OUTSIDE |
| | LIGHTS, EVEN 2ND FLOOR ARE. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |