| Plan Review Notes For Permit 06082188 |
| Permit Number |
06082188 |
|
| Review Stop |
B |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2007-09-14 09:44:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)THE STOREFRONT PRODUCT APPROVAL 05-0317.03 IS NOT | | | THE ONE REVIEWED BY DESIGNER OF RECORD (06-1019.08). | | | IF YOU WISH TO CHANGE PRODUCTS, SUBMIT AS A REVISION | | | AFTER REVIEW BY DESIGNER OF RECORD. | | | | | | 2.)THE NOAS SUBMITTED REQUIRE ENGINEERING ANALYSIS | | | DUE TO DESIGN WITH A 33% STRESS INCREASE WHICH IS NO | | | LONGER ALLOWED UNDER FBC2004.06-1019.08 PREVIOUSLY | | | REVIEWED BY DOR IS COMPLIANT AND DOES NOT REQUIRE THIS | | | ANALYSIS.PLEASE HAVE THE ENGINEER REVISE THE SHOP | | | DRAWINGS TO INDICATE THAT HE HAS REVIEWED ANCHORING | | | WITHOUT THE 33% STRESS INCREASE.SEE THE FLORIDA STATE | | | PRODUCT APPROVAL FOR PRODUCT 04-0227.02 AND SEE THE | | | NOAS WHICH STATE THAT A STRES INCREASE WAS USED IN | | | ANCHOR DESIGN. | | | | | | 3.)SHEET 4A STATES THAT DOOR 202.1 AND FRAME WILL BE | | | NONIMPACT.IS THIS AN INTERIOR DOOR? | | | |
|