| 2008-02-11 08:39:39 | ** DENIED REVISIONS ** |
| | |
| | 1) NOTE: PLEASE SEE PROVISO NOTES FROM MAY 07 HAVE NOT |
| | YET BEEN SUBMITTED FOR CORRECTIONS. PLEASE SEE NOTES |
| | ATTACHED TO THIS REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE THE REVISED ENERGY CALCULATIONS |
| | HAVE ITEMS WHICH NEED TO BE ADDRESSED. IN THE FOLLOWING |
| | NOTES THE INPUT DATA REPORT WILL BE NOTED AS IDR. |
| | |
| | A) ** PLEASE SEE THE SIGNATURE OF THE OWNER AGENT NEEDS |
| | TO BE SIGNED ON CERTIFICATION SHEETS. 13-103.1.1.1 |
| | |
| | B) ** PLEASE SEE THE LIGHTING AS SHOWN ON PLANS NEEDS |
| | TO COORDINATE WITH THE LIGHTING ON THE IDR. |
| | PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR DOES NOT |
| | MATCH WITH THE FIXTURE LEGEND ON PLANS, THE NUMBER OF |
| | FIXTURES OR THE WATTAGE OF FIXTURES. A FEW EXAMPLES |
| | WILL BE NOTED BELOW. |
| | PLEASE SEE FIXTURE SL3 WHICH IS 500WATTS ON IDR, IS |
| | ONLY 250WATTS ON FIXTURE LEGEND. |
| | PLEASE SEE THIS SAME SL3 FIXTURE ON THE IDR SHOWS ONLY |
| | THREE FIXTURES YET THE PLANS SHOW AT LEAST SEVEN. |
| | PLEASE SEE THE SL2 FIXTURES ON PLANS ARE NOT EVEN ON |
| | THE IDR. |
| | PLEASE SEE THE SL2 FIXTURE ALSO NEEDS TO SHOW WATTAGE |
| | OF FIXTURE ON FIXTURE LEGEND. |
| | PLEASE SEE THE CATEGORY FOR SL3 AND SL4 STATES |
| | *LIGHTING THAT IS SPECIFICALLY DESIGNATED AS REQUIRED |
| | BY A HEALTH, OR LIFE SAFETY STATUTE OR ORDINANCE*. |
| | PLEASE KNOW THERE IS NO SPECIFIC STATUTE, ORDINANCE, OR |
| | CODE WHICH THIS TYPE OF OUTSIDE LIGHTING IS REQUIRED. |
| | THERE IS SOME LIGHTING THAT IS REQUIRED BY STATUTES, |
| | HOWEVER THIS OCCUPANCY AND LOCATIONS DOES NOT FALL |
| | UNDER THIS. |
| | ** THIS WAS A FEW EXAMPLES, PLEASE BE SURE TO |
| | COORDINATE OTHERS AS WELL. |
| | |
| | 3) NOTE: PLEASE SUBMIT REVISED PHOTO-METRICS FOR |
| | REVISIONS IN THE LIGHTING PLANS. PLEASE KNOW THAT THE |
| | REVISED OUTSIDE LIGHTS DO NOT COORDINATE WITH THE |
| | LIGHTING FIXTURES AS SHOWN ON PHOTO-METRICS. NOT ALL |
| | BUT SOME ARE IN NEED OF BEING REVISED. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION/COORDINATION. |
| | |
| | PLEASE SUBMIT REVISED ITEMS. PLEASE BE SURE TO CALL IF |
| | THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE NOT |
| | UNDERSTOOD IN ANY FASHION. |
| | |