Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop E
Sequence Number 6
Notes
Date Text
2008-02-11 08:39:39** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE PROVISO NOTES FROM MAY 07 HAVE NOT
 YET BEEN SUBMITTED FOR CORRECTIONS. PLEASE SEE NOTES
 ATTACHED TO THIS REVIEW.
  
 2) NOTE: PLEASE SEE THE REVISED ENERGY CALCULATIONS
 HAVE ITEMS WHICH NEED TO BE ADDRESSED. IN THE FOLLOWING
 NOTES THE INPUT DATA REPORT WILL BE NOTED AS IDR.
  
 A) ** PLEASE SEE THE SIGNATURE OF THE OWNER AGENT NEEDS
 TO BE SIGNED ON CERTIFICATION SHEETS. 13-103.1.1.1
  
 B) ** PLEASE SEE THE LIGHTING AS SHOWN ON PLANS NEEDS
 TO COORDINATE WITH THE LIGHTING ON THE IDR.
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR DOES NOT
 MATCH WITH THE FIXTURE LEGEND ON PLANS, THE NUMBER OF
 FIXTURES OR THE WATTAGE OF FIXTURES. A FEW EXAMPLES
 WILL BE NOTED BELOW.
 PLEASE SEE FIXTURE SL3 WHICH IS 500WATTS ON IDR, IS
 ONLY 250WATTS ON FIXTURE LEGEND.
 PLEASE SEE THIS SAME SL3 FIXTURE ON THE IDR SHOWS ONLY
 THREE FIXTURES YET THE PLANS SHOW AT LEAST SEVEN.
 PLEASE SEE THE SL2 FIXTURES ON PLANS ARE NOT EVEN ON
 THE IDR.
 PLEASE SEE THE SL2 FIXTURE ALSO NEEDS TO SHOW WATTAGE
 OF FIXTURE ON FIXTURE LEGEND.
 PLEASE SEE THE CATEGORY FOR SL3 AND SL4 STATES
 *LIGHTING THAT IS SPECIFICALLY DESIGNATED AS REQUIRED
 BY A HEALTH, OR LIFE SAFETY STATUTE OR ORDINANCE*.
 PLEASE KNOW THERE IS NO SPECIFIC STATUTE, ORDINANCE, OR
 CODE WHICH THIS TYPE OF OUTSIDE LIGHTING IS REQUIRED.
 THERE IS SOME LIGHTING THAT IS REQUIRED BY STATUTES,
 HOWEVER THIS OCCUPANCY AND LOCATIONS DOES NOT FALL
 UNDER THIS.
 ** THIS WAS A FEW EXAMPLES, PLEASE BE SURE TO
 COORDINATE OTHERS AS WELL.
  
 3) NOTE: PLEASE SUBMIT REVISED PHOTO-METRICS FOR
 REVISIONS IN THE LIGHTING PLANS. PLEASE KNOW THAT THE
 REVISED OUTSIDE LIGHTS DO NOT COORDINATE WITH THE
 LIGHTING FIXTURES AS SHOWN ON PHOTO-METRICS. NOT ALL
 BUT SOME ARE IN NEED OF BEING REVISED.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION/COORDINATION.
  
 PLEASE SUBMIT REVISED ITEMS. PLEASE BE SURE TO CALL IF
 THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE NOT
 UNDERSTOOD IN ANY FASHION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]