Plan Review Notes
Plan Review Notes For Permit 06082188
Permit Number 06082188
Review Stop P
Sequence Number 5
Notes
Date Text
2008-06-05 10:44:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P1-01-101 & P1-02-101 HAVE BEEN SUBMITTED AS
 PHOTO COPIES AND WITH HAND DRAWN CHANGES TO ORIGINAL
 SIGNED, SEALED, DATED PLANS. ALL CHANGES TO SIGNED,
 SEALED & DATED PLANS SHALL BE SUBMITTED AS NEW
 REVISIONS, CLOUDED AND INDICATED WITH A REVISION NUMBER
 AND SHALL BE SIGNED, SEALED AND DATED BY THE ENGINEER
 OF RECORD. SECTION 106.1, FAC 61G15-23.002(2) & FS
 471.025.
  
 2. ALL CHANGES TO THE PLUMBING SANITARY, WATER, STORM,
 CONDENSATE, OR GAS SYSTEMS SHALL BE REFLECTED WITH
 REVISIONS TO THE ISOMETRIC RISER DIAGRAMS OF EACH
 SYSTEM THAT IS REVISED. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]